ELE08-00039
| DOC - Permit Finaled | 1/16/2009 | 1/16/2009 | 1/16/2009 12:18:36 PM | P | PASS |
|
|
|
ELE08-03235
| Electrical Rough-In | 1/15/2009 | 1/16/2009 | 1/16/2009 11:33:15 AM | A | PART |
|
|
jared - please call 1/2 hr prior for access Phone #: ###-#### Kitchen ok
|
ELE08-02914
| Electrical Rough-In | 1/15/2009 | 1/16/2009 | 1/16/2009 10:17:15 AM | A | PASS |
|
|
Kevin. Phone #: ###-#### Internet Inspection Request from: Lee Braithwait
|
ELE09-00089
| Electrical Rough-In | 1/15/2009 | 1/16/2009 | 1/16/2009 9:46:06 AM | A | CANC |
|
|
Please provide cover inspection for new wall inside of building. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean this is a state building and not under our juristriction
|
ELE09-00089
| DOC - Permit Expired | 1/16/2009 | 1/16/2009 | 1/16/2009 9:45:14 AM | A | PASS |
|
|
Please provide cover inspection for new wall inside of building. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean
|
ELE09-00062
| Electrical Rough-In | 1/15/2009 | 1/16/2009 | 1/16/2009 9:23:10 AM | A | FAIL |
|
|
jonese - Note: to cover Phone #: ###-#### found improper nail plating and stapleing undersized boxes burried outlet boxes cut-in boxes used where wiring not fished and clamps broken out of them.and outer sheath not in the box. open all wiring. for inspection.
|