Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00669 INSP-Final Inspection1/14/20131/16/20131/17/2013 11:59:53 AMAFAIL
permit finaled
FIR12-00741 INSP-Sprinkler Rough-in/Hydro1/16/20131/16/20131/16/2013 3:56:08 PMPCANC
Canceled due to time constraints. jeremy Phone #: ###-####
FIR12-00557 INSP-Alarm Testing1/16/20131/16/20131/16/2013 3:54:33 PMPFAIL
Retested and sent signals but none were received at central station. All so still need map and as-builts.
FIR12-00644 INSP-Final Inspection1/15/20131/16/20131/16/2013 3:52:16 PMPFAIL
Need a report of the signals sent today, as-builts showing the actual wiring of the dialer to the facp and verification sent to plan review to approve this wiring, and the duct smoke detectors repaired. Need signage on the facp room door as well.
FIR12-00744 INSP-Final Inspection1/15/20131/16/20131/16/2013 3:41:20 PMPCANC
Cancel per tim Phone #: ###-####
FIR12-00628 INSP-Final Inspection1/14/20131/16/20131/16/2013 12:48:30 PMAFAIL
The as-builts do not correctly show the actual branchline modified. Also many upright sprinkler heads are still covered with tape and one in the rear storage area has been painted.
FIR10-00429 INSP-Final Inspection1/15/20131/16/20131/16/2013 10:32:01 AMAPASS
Permit finaled
FIR10-00521 INSP-Final Inspection1/15/20131/16/20131/16/2013 9:18:14 AMAPASS
Permit finaled
BLD13-00039 FIRE-Final Inspection1/15/20131/16/20131/16/2013 9:13:18 AMAFAIL
Provide exit sign at the north exit, repair the exit sign in the kitchen, provide occupant load signs, provide fire extinguishers and provide re-certification for the hood suppression system when all of the appliances have been installed.