Inspections for the day of: Friday, January 16, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00096 Final1/16/20151/16/20151/16/2015 3:49:25 PMPFAIL
Per Jim Sly - Call Diana 30min prior at ###-####. Work done prior to moving in, need to know what needs to be done for final inspection
210.12- AFCI shall feed all outlets located in bed room.
Open ground at GFCI at bottom of stairs
ELE15-00110 Final1/15/20151/16/20151/16/2015 3:48:18 PMPPASS
Added bath fan to bath Phone #: ###-#### Inspection requested via web by Randy Fletcher Final ok
ELE15-00114 Electrical Rough-In1/15/20151/16/20151/16/2015 3:02:23 PMPPASS
Trenching inspection. Cal Doug at ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Barbara Szurgot Under slab just in front door rough in ok cover
ELE14-02082 Electrical Rough-In1/16/20151/16/20151/16/2015 2:44:54 PMPPASS
ceiling - Mike (bldg super) Phone #: ###-#### Office area grid rough in ok cover
ELE14-03292 Electrical Rough-In1/14/20151/16/20151/16/2015 2:18:07 PMPFAIL
Timothy Phone #: ###-#### Shall finish wiring 3-way,
300.4- Shall protect NM cable where ran through bored holes less than 1 1/4" from framing surface.Abrasion protection where NM cable enters panel.
Replace 3 wire dryer feed to 4- wire.
ELE15-00097 Final1/15/20151/16/20151/16/2015 1:05:36 PMAPART
Temporary final machine not on site yet need occupancy to bring machine in. Phone #: ###-#### Inspection requested via web by Thomas Jenkins No work performed in any other areas. Temp final ok
ELE15-00097 Electrical Rough-In1/16/20151/16/20151/16/2015 1:04:08 PMPPASS
Temporary final machine not on site yet need occupancy to bring machine in. Phone #: ###-#### Inspection requested via web by Thomas Jenkins Power feed to transformer and disconnecting means for laser machine and compressor. Rough in ok
ELE14-03551 Electrical Rough-In1/15/20151/16/20151/16/2015 12:26:30 PMAPASS
ceiling Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Entrance between Dillards and Kohls, just inside to right. Grid rough in ok cover.
ELE15-00113 Electrical Rough-In1/16/20151/16/20151/16/2015 12:18:30 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Inspection cancelled from web by: Lee VanSchoiack
ELE14-03112 Final1/15/20151/16/20151/16/2015 11:55:09 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan Service change Final ok
ELE13-01058 Electrical Rough-In1/16/20151/16/20151/16/2015 11:31:31 AMPCANC
we are also doing exterior lights to new DLC list UL/ETL listed LED at this building. Phone #: ###-#### >> Inspection requested via web by Tim Dunlop Inspection cancelled from web by: Tim Dunlop
ELE14-02318 Final1/16/20151/16/20151/16/2015 11:29:23 AMAPART
Brian Phone #: ###-#### Freezer area ok. Waiting on 2 cord end adapters for portable equiptment. 400.8 Flexible cord that powers fan on the exterior of existing portion of freezer shall be refed by a permanant wiring method and shall not be supported by metal water piping system. Available fault current shall be posted of new service gear.
ELE15-00115 Electrical Rough-In1/15/20151/16/20151/16/2015 10:39:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson Floor heat installed in entry hall, powder bath, kitchen, family rm, and laundry all controlled at bottom of stairs. Rough in ok cover
ELE14-02557 Final1/15/20151/16/20151/16/2015 9:56:23 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan Retaining wall final ok
ELE14-02943 Final1/15/20151/16/20151/16/2015 9:25:20 AMAFAIL
Josh is contact. Thanks Phone #: ###-#### Inspection requested via web by Chris Chesnut 210.8- All garage receptacle outlets 120 volt 15 -20 amp shall have GFCI protection.
210.8- Recetacle outlet in unfinished basement shall have GFCI protection.
210.70(A)(3)- Unfinished basement shall have at least 1 lighting outlet controlled by wall switch installed.
314.16- Island outlet boxes shall have sufficient capacity for conductors and device. 8ci box min of 10 needed.
410.16- Master closet luminaires shall have totally enclosed lamps.
* Master bath outlets dead.
* Unable to verify GFCI protection for master bath floor heat.
BCC- At least 50% of lamp shall be energy effient type.
ELE15-00083 Final1/15/20151/16/20151/16/2015 8:08:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Kelly Felin Service reconnect Final ok