ELE14-03498
| Final | 1/16/2015 | 1/16/2015 | 1/16/2015 3:08:20 PM | P | PASS |
|
|
Mark Phone #: ###-#### Final OK
|
ELE15-00106
| Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 2:48:35 PM | P | PASS |
|
|
Chris is contact. Just a little bit of work in lobby Thanks! Phone #: ###-#### Inspection requested via web by Chris Chesnut walls, 1 underground, 2 lights over underground stub, ok to cover
|
ELE15-00094
| Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 2:35:33 PM | P | PASS |
|
|
call for access Phone #: ###-#### Inspection requested via web by Mike Cole Kitchen remodel, Ok to cover
|
ELE15-00118
| Rough-In Permanent Service | 1/15/2015 | 1/16/2015 | 1/16/2015 1:56:51 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by michael hunts service not ready, OK to cover
|
ELE15-00118
| Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 1:56:31 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by michael hunt RI OK to cover
|
ELE14-03406
| Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 1:19:46 PM | P | PASS |
|
|
Garage is open and can be accessed via the alley. Call Tim if any issues Thank you
Phone #: ###-#### Inspection requested via web by John Harvey RI Ok to cover garage lower level only.
|
ELE14-03054
| Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 1:07:10 PM | P | PASS |
|
|
Calvin Phone #: ###-#### RI OK
|
ELE14-01374
| Final | 1/16/2015 | 1/16/2015 | 1/16/2015 12:51:22 PM | P | PASS |
|
|
Jay Phone #: ###-#### FInal OK
|
ELE14-02824
| Conference | 1/15/2015 | 1/16/2015 | 1/16/2015 12:18:41 PM | P | DONE |
|
|
Please schedule a conference to review electrical options in the kitchen area with Byron.
Thank you Phone #: ###-#### Inspection requested via web by Rhonda Zamagni discussed kitcher receptacle placement and exceeding placement requirements due to windows coming all the way down to countertop
|
ELE14-02525
| Final | 1/15/2015 | 1/16/2015 | 1/16/2015 11:49:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Final OK
|
ELE15-00095
| Electrical Rough-In | 1/15/2015 | 1/16/2015 | 1/16/2015 11:48:48 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Southwest corner of building, RI walls ok to cover, there were areas that were already covered with drywall
|
ELE15-00045
| Electrical Rough-In | 1/15/2015 | 1/16/2015 | 1/16/2015 10:49:19 AM | A | FAIL |
|
|
Ceiling cover inspection, call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson 300.11 independant means of secure support shall be provided, they shall be distinguishable by color ,tagging, or other means 300.11 cabling shall be supported by grid 358.30 emt shall be securely fastened within 3 ft. of boxes and conduit bodies 348.30 Flex shall be securely fastened within 12 inches of boxes and coduit bodies, and at intervals not exceeding 4 1/2 feet 110.12 unused openings shall be closed BCC 4.5.32 known code violations not to be retained
|
ELE14-01063
| Final | 1/15/2015 | 1/16/2015 | 1/16/2015 9:50:11 AM | A | FAIL |
|
|
Inspection requested via web by steve ragan corrections not addressed
|
ELE13-03115
| Final | 1/15/2015 | 1/16/2015 | 1/16/2015 9:18:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Final OK
|
ELE15-00109
| Final | 1/15/2015 | 1/16/2015 | 1/16/2015 9:07:03 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Gene Wright needed RI, wrong inspection type
|
ELE15-00109
| Electrical Rough-In | 1/16/2015 | 1/16/2015 | 1/16/2015 9:06:42 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gene Wright Wiring and trench from well head to detached garage, ok to cover
|
ELE13-01804
| Final | 1/15/2015 | 1/16/2015 | 1/16/2015 8:36:58 AM | A | PASS |
|
|
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden Ground replaced, Final OK
|