Inspections for the day of: Friday, January 16, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03498 Final1/16/20151/16/20151/16/2015 3:08:20 PMPPASS
Mark Phone #: ###-####
Final OK
ELE15-00106 Electrical Rough-In1/16/20151/16/20151/16/2015 2:48:35 PMPPASS
Chris is contact. Just a little bit of work in lobby
Thanks! Phone #: ###-#### Inspection requested via web by Chris Chesnut
walls, 1 underground, 2 lights over underground stub, ok to cover
ELE15-00094 Electrical Rough-In1/16/20151/16/20151/16/2015 2:35:33 PMPPASS
call for access Phone #: ###-#### Inspection requested via web by Mike Cole
Kitchen remodel, Ok to cover
ELE15-00118 Rough-In Permanent Service1/15/20151/16/20151/16/2015 1:56:51 PMPCANC
Phone #: ###-#### Inspection requested via web by michael hunts
service not ready, OK to cover
ELE15-00118 Electrical Rough-In1/16/20151/16/20151/16/2015 1:56:31 PMPCANC
Phone #: ###-#### Inspection requested via web by michael hunt
RI OK to cover
ELE14-03406 Electrical Rough-In1/16/20151/16/20151/16/2015 1:19:46 PMPPASS
Garage is open and can be accessed via the alley. Call Tim if any issues
Thank you

Phone #: ###-#### Inspection requested via web by John Harvey
RI Ok to cover garage lower level only.
ELE14-03054 Electrical Rough-In1/16/20151/16/20151/16/2015 1:07:10 PMPPASS
Calvin Phone #: ###-####
RI OK
ELE14-01374 Final1/16/20151/16/20151/16/2015 12:51:22 PMPPASS
Jay Phone #: ###-####
FInal OK
ELE14-02824 Conference1/15/20151/16/20151/16/2015 12:18:41 PMPDONE
Please schedule a conference to review electrical options in the kitchen area with Byron.

Thank you Phone #: ###-#### Inspection requested via web by Rhonda Zamagni
discussed kitcher receptacle placement and exceeding placement requirements due to windows coming all the way down to countertop
ELE14-02525 Final1/15/20151/16/20151/16/2015 11:49:19 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Final OK
ELE15-00095 Electrical Rough-In1/15/20151/16/20151/16/2015 11:48:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Southwest corner of building, RI walls ok to cover, there were areas that were already covered with drywall
ELE15-00045 Electrical Rough-In1/15/20151/16/20151/16/2015 10:49:19 AMAFAIL
Ceiling cover inspection, call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson
300.11 independant means of secure support shall be provided, they shall be distinguishable by color ,tagging, or other means
300.11 cabling shall be supported by grid
358.30 emt shall be securely fastened within 3 ft. of boxes and conduit bodies
348.30 Flex shall be securely fastened within 12 inches of boxes and coduit bodies, and at intervals not exceeding 4 1/2 feet
110.12 unused openings shall be closed
BCC 4.5.32 known code violations not to be retained
ELE14-01063 Final1/15/20151/16/20151/16/2015 9:50:11 AMAFAIL
Inspection requested via web by steve ragan
corrections not addressed
ELE13-03115 Final1/15/20151/16/20151/16/2015 9:18:35 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Final OK
ELE15-00109 Final1/15/20151/16/20151/16/2015 9:07:03 AMACANC
Phone #: ###-#### Inspection requested via web by Gene Wright
needed RI, wrong inspection type
ELE15-00109 Electrical Rough-In1/16/20151/16/20151/16/2015 9:06:42 AMPPASS
Phone #: ###-#### Inspection requested via web by Gene Wright
Wiring and trench from well head to detached garage, ok to cover
ELE13-01804 Final1/15/20151/16/20151/16/2015 8:36:58 AMAPASS
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden
Ground replaced, Final OK