Inspections for the day of: Tuesday, January 16, 2018.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-00210 Final1/16/20181/16/20181/16/2018 4:07:36 PMPCANC
Please have inspector call Aaron the installer before going out. ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd- will reschedule- wasnt ready per phone call
MEC17-04710 Final1/15/20181/16/20181/16/2018 3:46:52 PMPFAIL
Phone #: ###-#### Inspection requested via web by Konrad Swartz- both units need air balance redone below 80%
MEC18-00248 Pressure Test1/15/20181/16/20181/16/2018 3:28:17 PMPPASS
Pressure test is needed for the gas line. There also needs to be a pressure test for the furnace vent (pvc pipe). A gas line was run to the furnace, range, and dryer. Phone #: ###-#### Inspection requested via web by Steve Bunch- 2olb gas pass- 5lb flue pass
MEC18-00164 Final1/12/20181/16/20181/16/2018 3:12:24 PMPPASS
Please call homeowner 30 minutes in advance for access at ###-#### and call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Lea Briggs- furnace CO ok
MEC18-00243 Final1/15/20181/16/20181/16/2018 2:50:05 PMPPASS
please call Brad our lead installer when 30 mins in route Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace AC co ok
MEC17-02274 Final1/16/20181/16/20181/16/2018 2:19:54 PMPPASS
Please call 30 minutes in advance for access to ###-#### and call Eddie with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Lea Briggs- final ok should have been commerical permit not residential
MEC18-00119 Rough-in1/16/20181/16/20181/16/2018 1:46:29 PMPPASS
Mechanical Cover Inspection Needed PM today for Sanders Residence.If you have any questions please call Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- R/I ok
MEC18-00119 Pressure Test1/16/20181/16/20181/16/2018 1:46:01 PMPPASS
Mechanical Gas Pressure Test Inspection Needed PM today for Sanders Residence.If you have any questions please call Karl at ###-#### thank you. Phone #: ###-#### Inspection requested via web by Karl Hestekin- 20lb gas pass
MEC16-05255 Final1/12/20181/16/20181/16/2018 1:34:35 PMPPASS
homeowner needs to leave by 3pm to get her kids can someone please come before that time.

Thank you! Phone #: ###-#### Inspection requested via web by Marisa Hone- CO installed
MEC17-05640 Rough-in1/15/20181/16/20181/16/2018 11:22:10 AMAPASS
Grease duct Phone #: ###-#### Inspection requested via web by Nicholas Paige- weld on both ducts ok- ok for 1st layer of fire wrap
MEC18-00216 Pressure Test1/12/20181/16/20181/16/2018 11:18:40 AMAFAIL
PRESSURE WITNESS AND VENTING OF UNIT HEATER Phone #: ###-#### Inspection requested via web by Andrea Creek- gauge at zero- insulation shield on b vent needs 1" clearance
MEC17-04563 Final1/13/20181/16/20181/16/2018 11:05:28 AMAPASS
if needed knock on house door and ask for twain to gain access..final inspection Phone #: ###-#### Inspection requested via web by Ivan Marchello- unit heater and bath fan ok
MEC17-05824 Rough-in1/12/20181/16/20181/16/2018 10:40:04 AMAPASS
Rough in inspection for Dead on Archery Phone #: ###-#### Inspection requested via web by Matthew Benton- rough in ok- exposed duct ok- ok for cover
MEC17-05330 Final1/12/20181/16/20181/16/2018 10:23:04 AMPPASS
Phone #: ###-#### Inspection requested via web by Jasmin Godina
MEC18-00038 Rough-in1/12/20181/16/20181/16/2018 10:13:06 AMAFAIL
Phone #: ###-#### Inspection requested via web by Devony Bullard- need approved manual J onsite for inspection- Walked job with Vance- need transfers, framing complete around all ducting, insulation shield
MEC18-00037 Rough-in1/12/20181/16/20181/16/2018 10:11:52 AMAFAIL
Phone #: ###-#### Inspection requested via web by Devony Bullard- need approved manual J onsite for inspection- walked job with Vance
MEC17-05179 Final1/12/20181/16/20181/16/2018 10:11:05 AMANR
Phone #: ###-#### Inspection requested via web by Devony Bullard- need approved manual J onsite for inspection
MEC17-05177 Final1/12/20181/16/20181/16/2018 10:10:40 AMANR
Phone #: ###-#### Inspection requested via web by Devony Bullard- need approved manual J onsite for inspection
MEC18-00039 Rough-in1/12/20181/16/20181/16/2018 10:10:09 AMANR
Phone #: ###-#### Inspection requested via web by Devony Bullard- need approved manual J onsite for inspection
MEC18-00233 Rough-in1/12/20181/16/20181/16/2018 10:09:39 AMANR
Phone #: ###-#### Inspection requested via web by Devony Bullard- need approved manual J onsite
MEC17-05748 Rough-in1/12/20181/16/20181/16/2018 10:09:08 AMAFAIL
Phone #: ###-#### Inspection requested via web by Devony Bullard- need approved manual J onsite for inspection
MEC17-05701 Rough-in1/12/20181/16/20181/16/2018 9:13:48 AMAFAIL
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- need access frame in garage to access furnace- need 4" clearance in crawl on ducting and supported per manufacture requirements
MEC17-05701 Pressure Test1/12/20181/16/20181/16/2018 9:12:39 AMAPASS
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- 20lb gas pass
MEC17-02274 Mec-Aging Inspection1/16/20181/16/20181/16/2018 8:41:21 AM FAIL
need final inspection called in
MEC17-01030 Mec-Aging Inspection1/16/20181/16/20181/16/2018 8:40:33 AM PEND
contractor to schedule for final inspection
MEC17-02216 Rough-in1/15/20181/16/20181/16/2018 8:36:57 AMACANC
Light Test - Grease Duct - call Luke Phone #: ###-#### Inspection requested via web by Brandon Sorensen- reschedule for tomorrow am per phone call