BLD17-04081
| FIRE-Final Inspection | 1/16/2018 | 1/16/2018 | 1/16/2018 2:38:44 PM | P | FAIL |
|
|
The panic hardware still needs to be installed at the north exit doors
Jeff Phone #: ###-####
|
BLD17-03704
| FIRE-Final Inspection | 1/16/2018 | 1/16/2018 | 1/16/2018 2:21:14 PM | P | PASS |
|
|
life safety passed
Greg'' Phone #: ###-####
|
FIR17-00757
| INSP-Final Inspection | 1/15/2018 | 1/16/2018 | 1/16/2018 2:20:45 PM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by John Siewert
|
FIR17-00656
| INSP-Sprinkler Rough-in | 1/16/2018 | 1/16/2018 | 1/16/2018 2:04:03 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
Payton Phone #: ###-####
|
FIR18-00013
| INSP-Sprinkler Rough-in | 1/16/2018 | 1/16/2018 | 1/16/2018 1:40:56 PM | P | PASS |
|
|
The underground supply piping is ok for cover.
Bryan Collins is the contact for this underground rough-in. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR17-00454
| INSP-Sprinkler Rough-in | 1/15/2018 | 1/16/2018 | 1/16/2018 1:38:04 PM | A | PASS |
|
|
Underground supply line approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR17-00522
| INSP-Sprinkler Rough-in | 1/15/2018 | 1/16/2018 | 1/16/2018 12:44:46 PM | A | FAIL |
|
|
Inspection was for the 4th floor wet and dry system. For cover approval of the wet system I need tenting done and all drops sidewalls installed (need approval for exposed cpvc piping in chases). For cover approval of the dry system I need resubmittals due to additional fittings and pipe routing, need data sheet for the Concealed Space Heads because they may be mounted too low, need the longitudinal bracing installed as discussed.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR17-00691
| INSP-Final Inspection | 1/16/2018 | 1/16/2018 | 1/16/2018 12:40:32 PM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-02618
| FIRE-Final Inspection | 1/12/2018 | 1/16/2018 | 1/16/2018 12:39:55 PM | A | FAIL |
|
|
No city approved plans on site, most smoke alarms are located too close to bathroom doors, fire extinguishers are needed on each level or in each apartment as discussed.
Duane Phone #: ###-####
|