Inspections for the day of: Tuesday, January 16, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-04081 FIRE-Final Inspection1/16/20181/16/20181/16/2018 2:38:44 PMPFAIL
The panic hardware still needs to be installed at the north exit doors

Jeff Phone #: ###-####
BLD17-03704 FIRE-Final Inspection1/16/20181/16/20181/16/2018 2:21:14 PMPPASS
life safety passed

Greg'' Phone #: ###-####
FIR17-00757 INSP-Final Inspection1/15/20181/16/20181/16/2018 2:20:45 PMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by John Siewert
FIR17-00656 INSP-Sprinkler Rough-in1/16/20181/16/20181/16/2018 2:04:03 PMPPASS
Rough-in passed. Piping can be covered.

Payton Phone #: ###-####
FIR18-00013 INSP-Sprinkler Rough-in1/16/20181/16/20181/16/2018 1:40:56 PMPPASS
The underground supply piping is ok for cover.

Bryan Collins is the contact for this underground rough-in. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR17-00454 INSP-Sprinkler Rough-in1/15/20181/16/20181/16/2018 1:38:04 PMAPASS
Underground supply line approved for cover.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00522 INSP-Sprinkler Rough-in1/15/20181/16/20181/16/2018 12:44:46 PMAFAIL
Inspection was for the 4th floor wet and dry system. For cover approval of the wet system I need tenting done and all drops sidewalls installed (need approval for exposed cpvc piping in chases). For cover approval of the dry system I need resubmittals due to additional fittings and pipe routing, need data sheet for the Concealed Space Heads because they may be mounted too low, need the longitudinal bracing installed as discussed.


Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR17-00691 INSP-Final Inspection1/16/20181/16/20181/16/2018 12:40:32 PMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD17-02618 FIRE-Final Inspection1/12/20181/16/20181/16/2018 12:39:55 PMAFAIL
No city approved plans on site, most smoke alarms are located too close to bathroom doors, fire extinguishers are needed on each level or in each apartment as discussed.

Duane Phone #: ###-####