Inspections for the day of: Wednesday, January 16, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00835 INSP-Final Inspection1/15/20191/16/20191/16/2019 2:57:49 PMPFAIL
No testing of devices performed today. Inspection was only for the Basement area. Plan modifications are needed showing the correct form of communication, fire sprinkler riser device count (delete dry system), strobes are too low, wall and ceiling mount devices do not corrispond with the plans, Storage Room needs notification device modifications, batteries in the FACP do not match plans. We discussed the function of the Basement duct smoke detectors in the Mechanical Room.

Earl Lasater, Technician Phone #: ###-#### Inspection requested via web by John Siewert
FIR18-00435 INSP-Sprinkler Rough-in1/15/20191/16/20191/16/2019 11:04:02 AMAPART
Todays inspection was for the north half, first floor, of the building. I noted that not all of the additional 90's have been shown on the drawings or probably provided in the hydraulic calculations. I noted branchline restraints, earthquake bracing, and retaining straps are missing in most locations. It appears sprinkler protection will need to be added under the stairs east of the elevator. Also wood walls have been built in the non-combustible portion of the building and will need to be addressed as discussed. Plan mods will be needed for the added fittings to verify calculations. Combustible concealed spaces have not been addressed. No piping can be covered.


Josh Eaton is the contact for this RTC inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00937 INSP-Final Inspection1/15/20191/16/20191/16/2019 10:02:20 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
NAF18-00107 INSP-Final1/15/20191/16/20191/16/2019 10:02:01 AMADONE
Life safety passed

As late as possible Phone #: 2083319266 >> Inspection requested via mobile web by Dave Fotsch
BLD17-04590 FIRE-Final Inspection1/15/20191/16/20191/16/2019 9:54:25 AMAPASS
Life safety passed.

Randy Phone #: ###-####
FIR18-00609 INSP-Final Inspection1/15/20191/16/20191/16/2019 9:53:37 AMAPASS
Permit finaled

Roy Phone #: ###-####