Inspections for the day of: Thursday, January 16, 2020.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00207 Pressure Test1/15/20201/16/20201/16/2020 4:01:53 PMPNR
INSTALLER JOHN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- not ready
MEC19-05079 Final1/16/20201/16/20201/16/2020 2:53:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige
-final ok
MEC19-05080 Final1/16/20201/16/20201/16/2020 2:52:48 PMPPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige
-final ok
MEC19-05601 Final1/16/20201/16/20201/16/2020 2:36:53 PMPPASS
Phone #: ###-#### Inspection requested via web by Aaron Alandt
- final ok
- TAB report ok
MEC19-05259 Final1/16/20201/16/20201/16/2020 1:54:34 PMPPASS
Installer Matt took pictures of corrections and texted them to Jack Reynolds. For Final Inspection. Please call Carolyn at ###-#### if you have any questions. No need to return to home. Phone #: ###-#### Inspection requested via web by Carolyn Rudd
- final ok
MEC19-04655 Final1/15/20201/16/20201/16/2020 1:32:02 PMPFAIL
Thank you! Phone #: ###-#### Inspection requested via web by Denise Colin
- two fittings in new PVC flue are leaking condensate.
- fix leaking flue
- will need to witness 5lb flue pressure test for final. Reschedule a time with homeowner we can all meet to perform test.
MEC20-00144 Final1/16/20201/16/20201/16/2020 1:02:09 PMPPASS
Inspection requested via web by Margie Rowe
- final ok
MEC19-00240 Final1/15/20201/16/20201/16/2020 11:51:35 AMANR
Final Area A - Contact: ###-####. Phone #: ###-#### Inspection requested via web by Brent Lacy
- condensate for mini split in parking garage not finished
- documents for hydronics bypass ok
MEC19-04252 Final1/15/20201/16/20201/16/2020 11:12:08 AMAPASS
PLEASE CALL SHANE ###-#### TO MEET Phone #: ###-#### Inspection requested via web by SARA GREENHALGH
- final ok
MEC19-05371 Final1/15/20201/16/20201/16/2020 11:11:55 AMAPASS
PLEASE CALL SHANE ###-#### TO MEET Phone #: ###-#### Inspection requested via web by SARA GREENHALGH
- final ok
MEC20-00209 Pressure Test1/15/20201/16/20201/16/2020 10:41:50 AMAFAIL
Gauge outside Phone #: ###-#### Inspection requested via web by Mary LaFayette
- need protective coating on gas line penetration
- retest gas line once coating has been installed
MEC19-05713 Final1/15/20201/16/20201/16/2020 10:31:50 AMAFAIL
please call jake 30 min prior for access. Phone #: ###-#### Inspection requested via web by Nicholas Paige
- need to see mechanical permit for venting of pressure washer before final is given to gas line permit.
MEC19-02609 Final1/10/20201/16/20201/16/2020 9:40:09 AMAPASS
Please call Carrie on your way over. Thank you! Phone #: ###-#### Inspection requested via web by Misty Merry
- final ok
MEC19-05631 Final1/15/20201/16/20201/16/2020 9:30:18 AMAPASS
Please inspect after 9 AM Phone #: ###-#### Inspection requested via web by Mary LaFayette
- final ok
MEC19-05079 Final1/15/20201/16/20201/16/2020 8:58:36 AMAFAIL
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- A/C needs locking caps installed on service ports
- secondary drain needs pvc extended down to floor
MEC19-05080 Final1/15/20201/16/20201/16/2020 8:55:15 AMAFAIL
please call in advance for access Phone #: ###-#### Inspection requested via web by Nicholas Paige
- A/C needs locking caps installed on service ports
- secondary drain needs pvc extended down to floor
MEC20-00118 Final1/15/20201/16/20201/16/2020 8:06:53 AMAPASS
Corrections made Inspection requested via web by Margie Rowe
- final ok
MEC19-01186 Mec-Aging Inspection1/16/20201/16/20201/16/2020 8:04:37 AM PASS
Doc Permit Expired ok
MEC19-01186 DOC - Permit Expired1/16/20201/16/20201/16/2020 8:04:22 AMAPASS
Doc Permit Expired ok permit not active