Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00331 INSP-Final Inspection1/16/20031/17/20031/17/2003 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 01/16/2003 at 09:35:59. Contact: ###-####.
BLD02-02267 FIRE-Sprinkler Rough-in1/16/20031/17/20031/17/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 01/16/2003 at 14:04:25. Contact: ###-####. okay to cover - tenting complete 1/17/2003 8:29:05 AM
BLD02-02980 FIRE-Final Inspection1/16/20031/17/20031/17/2003 12:00:00 AMAPASS
###-#### okay for occupancy; has some penetrations to fix for structural inspector 1/17/2003 8:52:45 AM
FIR02-00507 INSP-Sprinkler Rough-in1/17/20031/17/20031/17/2003 12:00:00 AMAPART
okay to cover; tenting complete; riser not complete
FIR02-00488 INSP-Final Inspection1/17/20031/17/20031/17/2003 12:00:00 AMPFAIL
bruce; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie two sprinkler heads painted - located on both sides of the kitchen hood 1/17/2003 4:44:59 PM
BLD02-01928 FIRE-Final Inspection1/15/20031/17/20031/17/2003 12:00:00 AMPCANC
smoke detectors ###-#### ralph please call for access ran out of time rescheduled for 1/21 1/17/2003 4:51:28 PM
BLD02-01930 FIRE-Final Inspection1/15/20031/17/20031/17/2003 12:00:00 AMPCANC
###-#### ralph please call for access ran out of time; rescheduled for 1/21 1/17/2003 4:51:15 PM
BLD02-02112 FIRE-Final Inspection1/16/20031/17/20031/17/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 01/16/2003 at 15:03:48. Contact: ###-####. per Dave Miller temp occ is approved; need alarm plans submitted for addition of duct detectors monitored by FACP; smoke and pull are on two zones and can be combined to free up one zone for duct detectors on a four zone FireLite panel 1/17/2003 10:36:16 AM
FIR02-00509 INSP-Final Inspection1/16/20031/17/20031/17/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 01/16/2003 at 16:40:45. Contact: ###-####. overhead door not installed yet; will require reinspection to verify head is installed under the door 1/17/2003 10:33:56 AM
FIR02-00331 INSP-Final Inspection1/17/20031/17/20031/17/2003 12:00:00 AMPFAIL
NAC circuits aren't wired per plans; circuits at panels are mixed up; strobe not working wrestling room and room 209; door holders not releasing on alarm; need resubmittals for NAC wiring; need to test tampers and flows for both systems and complete testing of cafeteria 1/17/2003 4:47:38 PM
BLD02-02946 FIRE-Final Inspection1/17/20031/17/20031/17/2003 12:00:00 AMPCANC
gil; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie inspector ran out time rescheduled for 1/21 1/17/2003 4:51:00 PM