Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04252 Electrical Rough-In1/16/20061/17/20061/17/2006 4:45:50 PMPPASS
Scheduled by a contractor via Hello! on 1/16/2006 at 5:17:07 PM. Contact: ###-####. walls and ceilings ok
ELE06-00069 Electrical Rough-In1/17/20061/17/20061/17/2006 4:12:50 PMPFAIL
neal; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not made nail plates and 11/4" cor. posted called
ELE05-04038 Electrical Rough-In1/17/20061/17/20061/17/2006 3:48:52 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok
ELE05-04181 Permanent Service1/16/20061/17/20061/17/2006 2:59:30 PMAPASS
Scheduled by a contractor via Hello! on 1/16/2006 at 3:24:35 PM. Contact: ###-####. p/s u/g new ok
ELE05-04497 Permanent Service1/17/20061/17/20061/17/2006 2:22:30 PMPPASS
donna; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
p/s u/g new ok
ELE05-02785 Final1/16/20061/17/20061/17/2006 1:52:28 PMAFAIL
Scheduled by a contractor via Hello! on 1/16/2006 at 9:19:30 PM. Contact: ###-####. cor. posted met owner secure boxes to structure and install all fixtures outside lights, correct wiring recept in garage, needs connectors for cables at ceiling fixtures in garage
ELE06-00157 Temporary Service1/16/20061/17/20061/17/2006 1:30:11 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Joe Thomas cor. called use manufactures listed breakers only
ELE05-04293 Rough-In Permanent Service1/16/20061/17/20061/17/2006 1:18:58 PMAPASS
Scheduled by a contractor via Hello! on 1/16/2006 at 12:39:06 PM. Contact: ###-####. r/i ok p/s u/g new ok
ELE06-00015 Rough-In Permanent Service1/16/20061/17/20061/17/2006 1:03:58 PMAPASS
Scheduled by a contractor via Hello! on 1/16/2006 at 8:52:49 AM. Contact: ###-####. survey posted called grd boxes complete all makeup, #12 equip grd pigtail 2 gang box left of kit sink r/i ok
p/s u/g new ok
ELE06-00143 Temporary Service1/13/20061/17/20061/17/2006 11:13:54 AMAFAIL
allen-- ###-#### shall not use pvc for support of mast and change or bond metal weatherhead called
ELE06-00147 Electrical Rough-In1/17/20061/17/20061/17/2006 10:36:40 AMPDONE
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore was done in the AM
ELE05-04492 Final1/16/20061/17/20061/17/2006 10:12:36 AMADONE
Scheduled by a contractor via Hello! on 1/16/2006 at 3:23:19 PM. Contact: ###-####. done by 370
ELE06-00105 Permanent Service1/16/20061/17/20061/17/2006 9:42:42 AMAFAIL
Please call 1/2 before for access - Tim ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer see r/i notes
ELE06-00105 Electrical Rough-In1/16/20061/17/20061/17/2006 9:42:02 AMAFAIL
Please call 1/2 before for access - Tim ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer
cor. called 314.16 box fill 300.4 nail plates and 11/4", 250.66 all grds and bond #$, 250. 52(A)(1) or 104(A)(1) grd or bond water system 250.24 (A)(1) all grds and bonds shall terminate at neutral bus, 250.90,92 bond all raceways and nipples at p/s with #4, 250.56 needs 2 grd rods