Inspections for the day of: Tuesday, January 17, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00404 INSP-Sprinkler Rough-in1/17/20061/17/20061/17/2006 3:49:40 PMPPART
B and D third floors are ok to cover. The ceiling has been installed in unit C without a cover inspection for the sprinkler piping. I told the general contractor the ceiling would need to come out for this inspection.
BLD05-02382 FIRE-Final Inspection1/13/20061/17/20061/17/2006 3:43:02 PMPPASS
Life safety finaled
FIR05-00600 INSP-Sprinkler Rough-in1/17/20061/17/20061/17/2006 3:20:02 PMPPASS
underground supply piping is ok to cover
FIR05-00542 INSP-Supply line flush1/16/20061/17/20061/17/2006 2:14:50 PMACANC
No time for inspection. Per Brian it will be called in for tomorrow.
FIR05-00784 INSP-Sprinkler Rough-in1/17/20061/17/20061/17/2006 1:46:40 PMPPASS
Sprinkler piping is ok to cover
BLD05-02924 FIRE-Final Inspection1/17/20061/17/20061/17/2006 1:28:52 PMPFAIL
No inspection performed since the first item to be inspected failed which was the smoke evac system. It appears to be missing from the new tenant space. Fire extinguishers need tagged as well.
FIR05-00876 INSP-Sprinkler Rough-in1/17/20061/17/20061/17/2006 12:46:59 PMPFAIL
Need to add on upright head just to the west of the main entry and fix all of the falling insulation and backing.
BLD05-02014 FIRE-Final Inspection1/13/20061/17/20061/17/2006 12:15:21 PMAPART
A temporary occupancy was given with Dave Hannemans permission until the revised fire alarm plans are approved. Sprinkler permit needs finaled. Life safety will be ok to final when both fire permits are finaled and the new door has closer and seals.
FIR05-00676 INSP-Final Inspection1/17/20061/17/20061/17/2006 12:14:20 PMPPART
A temporary occupancy was given with Dave Hannemans permission until the revised fire alarm plans are approved. Pull stations and a/v's as installed work.
FIR05-00648 INSP-Final Inspection1/17/20061/17/20061/17/2006 12:11:48 PMPPART
A temporary occupancy was given until the fire alarm permit is approved. This permit needs finaled as well if correction have been made.
BLD05-03041 FIRE-Final Inspection1/13/20061/17/20061/17/2006 11:41:03 AMPFAIL
One sprinkler pendant is overspaced at the south end of the parts/storage area.
BLD05-03051 FIRE-Conference1/12/20061/17/20061/17/2006 11:03:34 AMADONE
This project has exiting issues which include door swing, exit hardware, exit signs and emergency lighting in the building and at the exit discharge. Also need one more fire extinguisher. Threshold at exit door is nearly 2" high.
BLD04-02149 FIRE-Final Inspection1/13/20061/17/20061/17/2006 10:23:01 AMAFAIL
###-#### SCOTT NOTE: PLEASE SEE HIM OR CALL
No one on the fourth floor knew anything about the job and I left a message on scotts voice mail
BLD05-02729 FIRE-Final Inspection1/13/20061/17/20061/17/2006 9:45:37 AMAPASS
Life safety finaled
FIR05-00667 INSP-Sprinkler Rough-in/Hydro1/16/20061/17/20061/17/2006 9:26:57 AMAPART
Scheduled by a contractor via Hello! on 1/16/2006 at 2:23:15 PM. Contact: ###-####.
FIR05-00465 INSP-Sprinkler Rough-in/Hydro1/16/20061/17/20061/17/2006 9:26:43 AMAPART
See city approved plans for areas inspected and areas left to inspect
FIR05-00864 INSP-Conference1/17/20061/17/20061/17/2006 12:00:00 AMPCANC
mitch; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles