Inspections for the day of: Wednesday, January 17, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02800 Permanent Service1/17/20071/17/20071/17/2007 4:25:19 PMPNH
Scheduled by a contractor via Hello! on 1/17/2007 at 7:54:19 AM. door to panel rm locked
ELE06-02854 Final1/17/20071/17/20071/17/2007 3:51:07 PMPFAIL
danny; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
no address called
ELE06-04593 Electrical Rough-In1/17/20071/17/20071/17/2007 3:33:17 PMPFAIL
Jeff; Phone #: ###-####, please call 1st Internet Inspection Request from: Cathy Weisshaupt corr. posted met owner same thing Pat told owner about, 300.14 6"free length, 314.16 box fill 300.4 nail plates and 11/4" for cables parallel
ELE07-00169 Electrical Rough-In1/17/20071/17/20071/17/2007 2:55:57 PMPFAIL
richard; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
corr. not made same violation pat noted 300.4(A)(1)&(D) nail plates and 11/4" for cables parallel to framing members
ELE06-03833 Final1/17/20071/17/20071/17/2007 1:23:49 PMPFAIL
phil; Phone #: ###-#### Internet Inspection Request from: Cathy
corr. fee due BCC owner did elect. work on contractor permit , shall open all boxes, all light fixtures, 408.4 panel schedule
ELE06-04435 Final1/17/20071/17/20071/17/2007 12:59:24 PMPNR
Phone #: ###-#### called
ELE06-04116 Electrical Rough-In1/16/20071/17/20071/17/2007 10:40:33 AMACANC
steve please call 10 min before going out .thanks; Phone #: ###-#### Internet Inspection Request from: Darla Downs

called left message
ELE07-00083 Rough-In Permanent Service1/16/20071/17/20071/17/2007 10:39:41 AMAFAIL
Electrical rough -in for new residential and permanent service Phone #: ###-####
corr. called 314.16 box fill , 300.4 nail plates and 11/4'' 210.52(A) outlet spacing and 2ft walls, 110.14 bond screws are loose, also using wrong tool for crip sleeves, 250.148 splice all equip grds together 12 and 14 210.11, 210.52(F) all outlets in laundry rm shall be 20 amp, 210.52(B)(1) shall not have switched lighting outlets on S A B C in din rmm outlet outside back not wired, partial corr. only job not ready COW
ELE06-03513 Electrical Rough-In1/16/20071/17/20071/17/2007 9:35:01 AMAPART
Phone #: ###-#### ceilings ok
ELE07-00141 Electrical Rough-In1/16/20071/17/20071/17/2007 9:21:11 AMAFAIL
christina; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
see added conference, 300.4 nail plates and 11/4" 300.16 box fill, 300.14 6" free length, 210.52(A) outlet spacing
ELE07-00141 Conference1/17/20071/17/20071/17/2007 9:19:47 AMADONE
christina; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
01 ok
ELE06-03351 Final1/16/20071/17/20071/16/2007 1:24:49 PMAPASS
On site journeyman - Randy ###-####. Please call if problems Phone #: ###-####
ok no card