ELE06-02800
| Permanent Service | 1/17/2007 | 1/17/2007 | 1/17/2007 4:25:19 PM | P | NH |
|
|
Scheduled by a contractor via Hello! on 1/17/2007 at 7:54:19 AM. door to panel rm locked
|
ELE06-02854
| Final | 1/17/2007 | 1/17/2007 | 1/17/2007 3:51:07 PM | P | FAIL |
|
|
danny; Phone #: ###-#### Internet Inspection Request from: Victoria Beall no address called
|
ELE06-04593
| Electrical Rough-In | 1/17/2007 | 1/17/2007 | 1/17/2007 3:33:17 PM | P | FAIL |
|
|
Jeff; Phone #: ###-####, please call 1st Internet Inspection Request from: Cathy Weisshaupt corr. posted met owner same thing Pat told owner about, 300.14 6"free length, 314.16 box fill 300.4 nail plates and 11/4" for cables parallel
|
ELE07-00169
| Electrical Rough-In | 1/17/2007 | 1/17/2007 | 1/17/2007 2:55:57 PM | P | FAIL |
|
|
richard; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. not made same violation pat noted 300.4(A)(1)&(D) nail plates and 11/4" for cables parallel to framing members
|
ELE06-03833
| Final | 1/17/2007 | 1/17/2007 | 1/17/2007 1:23:49 PM | P | FAIL |
|
|
phil; Phone #: ###-#### Internet Inspection Request from: Cathy corr. fee due BCC owner did elect. work on contractor permit , shall open all boxes, all light fixtures, 408.4 panel schedule
|
ELE06-04435
| Final | 1/17/2007 | 1/17/2007 | 1/17/2007 12:59:24 PM | P | NR |
|
|
Phone #: ###-#### called
|
ELE06-04116
| Electrical Rough-In | 1/16/2007 | 1/17/2007 | 1/17/2007 10:40:33 AM | A | CANC |
|
|
steve please call 10 min before going out .thanks; Phone #: ###-#### Internet Inspection Request from: Darla Downs
called left message
|
ELE07-00083
| Rough-In Permanent Service | 1/16/2007 | 1/17/2007 | 1/17/2007 10:39:41 AM | A | FAIL |
|
|
Electrical rough -in for new residential and permanent service Phone #: ###-#### corr. called 314.16 box fill , 300.4 nail plates and 11/4'' 210.52(A) outlet spacing and 2ft walls, 110.14 bond screws are loose, also using wrong tool for crip sleeves, 250.148 splice all equip grds together 12 and 14 210.11, 210.52(F) all outlets in laundry rm shall be 20 amp, 210.52(B)(1) shall not have switched lighting outlets on S A B C in din rmm outlet outside back not wired, partial corr. only job not ready COW
|
ELE06-03513
| Electrical Rough-In | 1/16/2007 | 1/17/2007 | 1/17/2007 9:35:01 AM | A | PART |
|
|
Phone #: ###-#### ceilings ok
|
ELE07-00141
| Electrical Rough-In | 1/16/2007 | 1/17/2007 | 1/17/2007 9:21:11 AM | A | FAIL |
|
|
christina; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see added conference, 300.4 nail plates and 11/4" 300.16 box fill, 300.14 6" free length, 210.52(A) outlet spacing
|
ELE07-00141
| Conference | 1/17/2007 | 1/17/2007 | 1/17/2007 9:19:47 AM | A | DONE |
|
|
christina; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 01 ok
|
ELE06-03351
| Final | 1/16/2007 | 1/17/2007 | 1/16/2007 1:24:49 PM | A | PASS |
|
|
On site journeyman - Randy ###-####. Please call if problems Phone #: ###-#### ok no card
|