MIS17-00013
| ELE-Conference | 1/17/2017 | 1/17/2017 | 1/17/2017 3:00:40 PM | P | PASS |
|
|
Possible work being done without permits (BLD, ELE, MEC and PLM)...
posted stop work order...electrical wiring done without permit, new windows being install without permits and plumbing work done without permits
|
ELE17-00075
| Conference | 1/13/2017 | 1/17/2017 | 1/17/2017 2:14:12 PM | P | PASS |
|
|
would like call ahead; judy Phone #: ###-####....
discussed repacing service mast for shop service....addition of ground rod, new grounding electrode conductor, clearance for side of shop, length of riser, wire size for overhead 200 amp service, addition of guide wire kit on riser, and max highth of riser above shop rough
|
ELE17-00111
| Rough-In Permanent Service | 1/17/2017 | 1/17/2017 | 1/17/2017 1:05:17 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve cooper....
1) can above sink cannot be wired off small appliance circuit or dishwasher disposal circuit 210.52(B)(2) 422.10
2) where NM cable is used the sheath shall extend not less than 1/4" inside the box 314.17(C).....throught house- mst bed switches, smoke detector in upstairs bedroom, and various other locations
|
ELE13-00382
| ELE-Aging Inspection | 1/17/2017 | 1/17/2017 | 1/17/2017 11:41:36 AM | | DONE |
|
|
notice posted at address that a final inspection needs requested or extension of permit is required
|
ELE16-01961
| Permanent Service | 1/13/2017 | 1/17/2017 | 1/17/2017 11:09:04 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton....
p/s n ok
|
ELE16-01961
| Electrical Rough-In | 1/13/2017 | 1/17/2017 | 1/17/2017 11:08:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...
rough in complete upstairs wall cover
|
ELE17-00088
| Final | 1/16/2017 | 1/17/2017 | 1/17/2017 10:26:11 AM | A | CANC |
|
|
Temp pole Phone #: ###-#### Inspection requested via web by Kevin Burke...
needed temp service inspection
|
ELE17-00088
| Temporary Service | 1/17/2017 | 1/17/2017 | 1/17/2017 10:25:22 AM | A | PASS |
|
|
Temp pole Phone #: ###-#### Inspection requested via web by Kevin Burke..
t/s u/g n ok
|
ELE17-00087
| Electrical Rough-In | 1/14/2017 | 1/17/2017 | 1/17/2017 10:11:47 AM | A | PASS |
|
|
Inspection requested via web by David Seilheimer....
ok to cover
|
ELE16-02916
| Final | 1/13/2017 | 1/17/2017 | 1/17/2017 9:46:09 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Thomas wilson...
final ok
|
ELE17-00078
| Final | 1/13/2017 | 1/17/2017 | 1/17/2017 9:36:24 AM | A | PASS |
|
|
Contact Miles for questions ###-#### Phone #: ###-#### Inspection requested via web by Sheri Berry....
replaced 6 existing lights and added 4...ok to final
|
ELE17-00057
| Electrical Rough-In | 1/15/2017 | 1/17/2017 | 1/17/2017 9:19:52 AM | A | PASS |
|
|
Please call Kyle Lott of Lott Electric INC, for any question. Have a very bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott...
rough in wall cover only
|
ELE16-03280
| Final | 1/16/2017 | 1/17/2017 | 1/17/2017 8:59:51 AM | A | FAIL |
|
|
ANY QUESTIONS, PLEASE CALL TATE AT ###-#### Phone #: ###-#### Inspection requested via web by JENNY EMEL...
kitchen outlet reads hot neutral reverse
hood needs installation complete...exposed wires
outside sub panel needs labelling
breaker lockouts need installed on hard wired appliances
overcurrent device on heat pump is to large
|