BLD16-02141
| FIRE-Final Inspection | 1/17/2017 | 1/17/2017 | 1/17/2017 3:23:40 PM | P | PASS |
|
|
Life safety passed
|
BLD16-01291
| FIRE-Final Inspection | 1/16/2017 | 1/17/2017 | 1/17/2017 3:23:03 PM | P | FAIL |
|
|
Need the project related fire alarm and fire sprinkler permits finaled and the exit discharge light over the main exit repaired. I also discussed the need for the Opticom for the electric main gate prior to a final sign off for the entire project. See note 13 of the building A review comments.
|
FIR16-00646
| INSP-Final Inspection | 1/17/2017 | 1/17/2017 | 1/17/2017 2:48:34 PM | P | FAIL |
|
|
Need as-builts showing cellular dialer instead of phone lines and the two new tamper switches and the two fire sprinkler tamper switches wired in/tested.
|
FIR16-00455
| INSP-Final Inspection | 1/17/2017 | 1/17/2017 | 1/17/2017 2:47:25 PM | P | PASS |
|
|
permit finaled
|
FIR16-00455
| INSP-Supply line flush | 1/17/2017 | 1/17/2017 | 1/17/2017 2:47:08 PM | P | PASS |
|
|
Underground flush passed
|
FIR16-00640
| INSP-Final Inspection | 1/17/2017 | 1/17/2017 | 1/17/2017 2:46:47 PM | P | FAIL |
|
|
Provide the two additional tamper switches for the backflow preventor and the test papers.
|
BLD17-00023
| FIRE-Final Inspection | 1/17/2017 | 1/17/2017 | 1/17/2017 12:34:11 PM | P | PASS |
|
|
life safety passed
|
FIR16-00704
| INSP-Sprinkler Rough-in/Hydro | 1/16/2017 | 1/17/2017 | 1/17/2017 12:33:15 PM | A | PASS |
|
|
200 lb overhead hydro test passed
|
FIR16-00644
| INSP-Sprinkler Rough-in | 1/16/2017 | 1/17/2017 | 1/17/2017 10:03:23 AM | A | PASS |
|
|
See the city approved plans for locations where sprinkler piping on the first floor is ok to cover. Also see acouple of locations where minor corrections are needed.
|
BLD16-00372
| FIRE-Final Inspection | 1/13/2017 | 1/17/2017 | 1/17/2017 10:02:25 AM | A | FAIL |
|
|
Relocate the third fire extinguisher as discussed to the south exit. Contact plan review for direction on the three doors with keyed deadbolts
|
BLD16-03819
| FIRE-Final Inspection | 1/15/2017 | 1/17/2017 | 1/17/2017 8:27:32 AM | A | PASS |
|
|
life safety passed
|