BLD18-03690
| FIRE-Final Inspection | 1/16/2019 | 1/17/2019 | 1/17/2019 3:21:02 PM | P | PASS |
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by Will Thomason
|
BLD18-03595
| FIRE-Final Inspection | 1/16/2019 | 1/17/2019 | 1/17/2019 12:39:50 PM | A | PASS |
|
|
Life safety passed. One plan shows exit sign at door from warehouse to office, another plan does not show this exit sign. Currently there is no exit sign installed. May be required at occupancy. This permit is for Vanilla Finish, no occupancy.
Shawn Phone #: ###-####
|
FIR18-00794
| INSP-Final Inspection | 1/16/2019 | 1/17/2019 | 1/17/2019 10:41:14 AM | P | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00435
| INSP-Sprinkler Rough-in | 1/16/2019 | 1/17/2019 | 1/17/2019 10:40:12 AM | A | PART |
|
|
Todays inspection was for the remaining building except for the canopies and the garage/risers. As per the previous inspection branchline restraints are missing and additional 90's have been added that need to be included in on the hydraulic calculations. Piping above the hardlids in the Hospital portion of the building is ok for cover. Wall in the other portions of the building are ok to be covered as long as it does not cover any concealed pockets. There is stil the issue of the Concealed Space sprinkler heads on the second floor that need resolved.
Phone #: ###-#### Inspection requested via web by Stan Beus
|