Inspections for the day of: Friday, January 17, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00602 Conference1/17/20201/17/20201/17/2020 2:00:48 PMPDONE
Discussed the occupancy of parking garage in 30 days. General contractor will meet with city officials to determine a completion plan.
BLD18-01831 states several subs will finish on hotel phase including electrical lighting and emergency lighting, generator back up, elevators, egress paths ect.
Completion plan will determine what systems must be complete.
MIS19-00059 ELE-Final1/17/20201/17/20201/17/2020 1:53:24 PMPPASS
Able to confirm correction has been done by solar contractor. Final ok
ELE20-00176 Permanent Service1/16/20201/17/20201/17/2020 11:29:03 AMAPASS
Bush will be removed.
Thanks Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Service lower to compliant height, bush removed to short stumps. p/s o/h rec ok
ELE19-00601 Electrical Rough-In1/16/20201/17/20201/17/2020 11:02:17 AMAPASS
Fifth floor wall and ceiling cover hotel. Contact is Danny Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 5 units 502 thru 524 walls and fire lids, West corridor walls and fire lids, south corridor fire lid only rough in ok cover.
ELE19-04338 Electrical Rough-In1/16/20201/17/20201/17/2020 10:14:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed GFCI protection of kitchen receptacles, All receptacles will require GFCI protection in commercial kitchens as per 210.8(B). 3 pole appliance ok to hardwire and provide a disconnecting means if contractor chooses due to GFCI devices are not available at 35 amp rating.
Kitchen grid rough in ok cover.
ELE20-00157 Final1/16/20201/17/20201/17/2020 9:53:11 AMAPASS
Please call Lynn prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor
This work not associated with BLD19-03683, lighting upgrade so space can be used for temp space while condtruction is taking place.
Final ok
ELE20-00126 Final1/16/20201/17/20201/17/2020 9:32:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok