Inspections for the day of: Friday, January 18, 2002.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00418 INSP-Final Inspection1/17/20021/18/20021/18/2002 12:00:00 AMAPASS
Underground sprinkler line finaled 1/17/2002 2:00:48 PM
FIR01-00499 INSP-Final Inspection1/17/20021/18/20021/18/2002 12:00:00 AMAFAIL
Contractor needs to resubmit showing substitution of spot detectors for duct detectors in "Mens Warehouse", HVAC unit in "Billiards and BarStools" does not shut down, provide map of device locations and addresses at the FACP 1/18/2002 11:48:31 AM
BLD01-02787 FIRE-Final Inspection1/17/20021/18/20021/18/2002 12:00:00 AMAPASS
Fire life/safety finaled 1/18/2002 11:49:23 AM
BLD01-02791 FIRE-Final Inspection1/18/20021/18/20021/18/2002 12:00:00 AMPPASS
Fire life/safety finaled 1/18/2002 3:37:52 PM
BLD01-03001 FIRE-Final Inspection1/18/20021/18/20021/18/2002 12:00:00 AMPPASS
Added by Inspector: 430 On 1/18/2002 1:12:15 PM Fire life/safety finaled
BLD01-02584 FIRE-Final Inspection1/18/20021/18/20021/18/2002 12:00:00 AMPFAIL
Added by Inspector: 430 On 1/18/2002 2:09:44 PM The maximum storage height of 10' has been exceeded. Notified store manager that product will need to be taken off of top shelf. I told manager I will be back next week to re-inspect