FIR04-00574
| INSP-Final Inspection | 1/17/2005 | 1/18/2005 | 1/18/2005 11:34:45 AM | P | CANC |
|
|
Troy, We would like to schedule an inspection for this building sometime on Tuesday afternoon. Please call me at the office (###-####) or on my cell at (###-####) and let us know when is a good time for you. Thank you for your time. Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
BLD04-01727
| FIRE-Final Inspection | 1/17/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 1/18/2005 9:38:56 AM
|
FIR04-00806
| INSP-Final Inspection | 1/18/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | A | PASS |
|
|
Fire suppression system operated correctly
|
BLD04-02804
| FIRE-Final Inspection | 1/18/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | P | FAIL |
|
|
Life safety ok except for the existing 15cd a/v in the corridor needs relocated to be within 15' of each end of the corridor or changed to a 75cd device. Testing required but no permit.
|
FIR04-00626
| INSP-Sprinkler Rough-in/Hydro | 1/17/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | P | PASS |
|
|
Overhead hydro test passed 1/18/2005 3:38:36 PM
|
FIR04-00626
| INSP-Final Inspection | 1/17/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | P | FAIL |
|
|
Need interconnections with the fire alarm system tested and the 200 degree upright in the riser room replaced with at 155 1/18/2005 3:57:38 PM
|
BLD04-01911
| FIRE-Final Inspection | 1/18/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | P | PART |
|
|
A temporary occupancy was given. Need updated air balance reports and appliance layout 1/18/2005 11:03:04 AM
|
BLD04-00838
| FIRE-Final Inspection | 1/18/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | P | CANC |
|
|
Per contractor, he actually needed a cover inspection from the structural inspector. 1/18/2005 2:48:46 PM
|
FIR05-00006
| INSP-Final Inspection | 1/18/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 1/18/2005 at 10:10:30 AM. Contact: ###-####.
|
BLD04-02687
| FIRE-Final Inspection | 1/18/2005 | 1/18/2005 | 1/18/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 1/18/2005 12:10:03 PM
|