ELE06-00164
| Electrical Rough-In | 1/18/2006 | 1/18/2006 | 1/19/2006 9:08:57 AM | P | PASS |
|
|
roger; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corrections made, ric ok
|
ELE05-02708
| ELE-Aging Inspection | 1/18/2006 | 1/18/2006 | 1/18/2006 4:37:17 PM | | NR |
|
|
called contr to schedule an inspection and send some one to show what done
|
ELE05-04578
| Electrical Rough-In | 1/18/2006 | 1/18/2006 | 1/18/2006 4:21:19 PM | P | PASS |
|
|
inspection for room above garage//richard; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left survey, 314.23(B)(1) screws shall not pass thru interior of box-shall attach with brackets on outside of box-left side door upstairs over garage
|
ELE06-00166
| Final | 1/18/2006 | 1/18/2006 | 1/18/2006 4:10:51 PM | P | FAIL |
|
|
TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, left corr notice, 110.12(C) electrical equipment shall not be damaged-ground term burnt up, ko broken out shall be repaired-gec, there shall be no contamination-meter socket
|
ELE06-00128
| Temporary Service | 1/18/2006 | 1/18/2006 | 1/18/2006 4:08:16 PM | P | FAIL |
|
|
inspection for temp power for temp trailer. I (Todd Hall) spoke with Jim Schmer about placing the temp power for the trailer, on the Firestation building. Please call me if any questions; Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice,312.5 conductors entering enclosures shall have abrasion protection,250.92(B)(4) bonding jumpers shall be used around concentrics, 230.2(E) service disconnects shall be identified, 408.4 circuit directory shall be supplied at tlr #1, 352.30 rnc shall be supported at tlr #1, 408.7 unused openings shall be closed at tlr #2, 110.12(A) conduit openings shall be closed at tlr #2
|
ELE05-03703
| Electrical Rough-In | 1/18/2006 | 1/18/2006 | 1/18/2006 3:06:02 PM | P | PART |
|
|
Underground inspection. Thanks.; Phone #: ###-#### Internet Inspection Request from: Steve Syltie u/g first fl computer fl ok to cover
|
ELE06-00050
| Permanent Service | 1/18/2006 | 1/18/2006 | 1/18/2006 2:44:31 PM | P | PASS |
|
|
tolly ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok, will look at rest of job later
|
ELE05-04496
| Final | 1/17/2006 | 1/18/2006 | 1/18/2006 12:45:26 PM | P | PASS |
|
|
cliff; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-04496
| Permanent Service | 1/17/2006 | 1/18/2006 | 1/18/2006 12:44:30 PM | P | PASS |
|
|
cliff; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s u/g reconnect ok
|
ELE06-00179
| Electrical Rough-In | 1/17/2006 | 1/18/2006 | 1/18/2006 10:07:47 AM | A | PASS |
|
|
rick ###-#### file room walls and ceiling ok to cover
|
ELE05-02546
| ELE-Aging Inspection | 1/18/2006 | 1/18/2006 | 1/18/2006 9:52:00 AM | | DONE |
|
|
see final
|
ELE05-03058
| Conference | 1/17/2006 | 1/18/2006 | 1/18/2006 9:41:53 AM | A | DONE |
|
|
james-- call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie reviewed outlet spacing, circuiting, gfci, afci, smokes,etc
|
ELE05-04301
| Final | 1/17/2006 | 1/18/2006 | 1/18/2006 8:46:55 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/17/2006 at 1:48:35 PM. Contact: ###-####. ok to final, signed struct card
|
ELE05-04559
| Final | 1/17/2006 | 1/18/2006 | 1/18/2006 8:16:38 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/17/2006 at 3:16:57 PM. Contact: ###-####. ok to final, signed card
|
ELE05-02503
| Final | 1/18/2006 | 1/18/2006 | 1/18/2006 12:00:00 AM | A | PASS |
|
|
looked at signs, ok to final
|
ELE05-02372
| Final | 1/18/2006 | 1/18/2006 | 1/18/2006 12:00:00 AM | A | PASS |
|
|
ok t final
|
ELE05-02546
| Final | 1/18/2006 | 1/18/2006 | 1/18/2006 12:00:00 AM | A | PASS |
|
|
ok to final
|