MEC06-00201
| Final | 1/18/2006 | 1/18/2006 | 1/18/2006 4:13:49 PM | P | FAIL |
|
|
PLEASE CALL ME BEFORE GOING OUT AT ###-####, THANKS, ANDREA.; Phone #: ###-#### Internet Inspection Request from: Andrea Creek
|
MEC06-00201
| Pressure Test | 1/18/2006 | 1/18/2006 | 1/18/2006 4:13:31 PM | P | FAIL |
|
|
PLEASE CALL ME BEFORE GOING OUT AT ###-####, THANKS, ANDREA.; Phone #: ###-#### Internet Inspection Request from: Andrea Creek incorrect gas sizing, new 3/4" to be hooked to 1" gas line, retest system
|
MEC06-00176
| Pressure Test | 1/16/2006 | 1/18/2006 | 1/18/2006 4:12:06 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Donna Bledsoe need to install regulator at appliance, reroute gas line and retest
|
MEC06-00199
| Pressure Test | 1/18/2006 | 1/18/2006 | 1/18/2006 2:57:12 PM | P | PASS |
|
|
###-#### - todd
|
MEC06-00199
| Rough-in | 1/18/2006 | 1/18/2006 | 1/18/2006 2:56:53 PM | P | FAIL |
|
|
###-#### - todd draft stop return at ceiling to closet wall, stud is redmarked to show location on site, need 1" clearance to b-vent at stud in garage, verify combustion air location
|
MEC05-02781
| Final | 1/18/2006 | 1/18/2006 | 1/18/2006 2:35:47 PM | P | PASS |
|
|
###-#### - linda/dan
|
MEC06-00173
| Rough-in | 1/16/2006 | 1/18/2006 | 1/18/2006 2:03:56 PM | P | PASS |
|
|
please call homeowner before you go out at ###-####; Phone #: ###-#### Internet Inspection Request from: Andrea Creek
|
MEC06-00155
| Conference | 1/17/2006 | 1/18/2006 | 1/18/2006 10:35:52 AM | A | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore answer questions
|
MEC05-03724
| Final | 1/17/2006 | 1/18/2006 | 1/18/2006 9:46:50 AM | A | FAIL |
|
|
###-####- pj need protection post at furnace and draft collar at flue
|
MEC05-03340
| Final | 1/17/2006 | 1/18/2006 | 1/18/2006 9:31:54 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/17/2006 at 6:14:50 PM. Contact: ###-####.
|
MEC06-00195
| Rough-in | 1/17/2006 | 1/18/2006 | 1/18/2006 9:03:09 AM | A | FAIL |
|
|
Please contact job foreman, Denton Fuerher- ###-####. Internet Inspection Request from: RaChelle Meister c/n posted
|