BLD03-01020
| BLD-Aging Inspection | 1/18/2008 | 1/18/2008 | 1/24/2008 1:51:54 PM | P | DEFR |
|
|
Inspection scheduled.
|
BLD03-02347
| BLD-Aging Inspection | 1/18/2008 | 1/18/2008 | 1/23/2008 2:58:17 PM | P | DONE |
|
|
Site inspection scheduled.
|
BLD07-02703
| FIRE-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 4:17:31 PM | P | PASS |
|
|
Fire life safety passed, fire alarm modifications indicated on the permit application are not required and have not been installed-no FA permit issued due to no modifications made.
|
BLD07-02703
| FIRE-Alarm Testing | 1/17/2008 | 1/18/2008 | 1/18/2008 4:14:07 PM | P | DONE |
|
|
Not applicable to this project.
|
FIR07-00815
| INSP-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 4:10:56 PM | P | PASS |
|
|
See last entry..permit Finaled. KR
|
FIR07-00815
| FIR-Aging Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 3:54:31 PM | | PASS |
|
|
This permit passed during the testing of the kitchen hood system.Connection to the main fire alarm to the kitchen suppression system was verified and tested. KR
|
FIR07-00593
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 2:49:58 PM | A | PASS |
|
|
Final passed, flow switch cover attatched while on site, tape and paper at one garage sw to be removed when painting is finished, CPVC at the riser to meet mfg. installation guidelines.
|
FIR07-00879
| INSP-Sprinkler Rough-in | 1/17/2008 | 1/18/2008 | 1/18/2008 2:47:49 PM | A | PART |
|
|
Ok to cover remaining under ground piping.
|
FIR07-01023
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 2:46:29 PM | P | PASS |
|
|
Fire sprinkler work is satisfactory, final inspection okay, permit finaled.
|
BLD07-02964
| FIRE-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 1:48:49 PM | A | PASS |
|
|
No sprinkler work needed for this permit. Sprinklers were exsisting, no changes made.Life safety complete. KR
|
BLD08-00089
| FIRE-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 1:25:30 PM | P | PASS |
|
|
Necessary correction completed, fire life safety inspection passed.
|
FIR07-01004
| INSP-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 1:24:28 PM | P | PASS |
|
|
Required correction and system/plan modification passed inspection, permit finaled.
|
FIR07-00989
| INSP-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 12:56:11 PM | P | CANC |
|
|
Overbooked, inspection rescheduled.
|
FIR07-00472
| INSP-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 12:37:32 PM | P | FAIL |
|
|
Need to change descriptor for the smoke detector at the electrical closet, , damper at suite 504 did not close upon actuation of the ID detector, addresses at the in duct detectors for the shell and core devices between units 501 and 502 are not accurate (duplicated elsewhere).
|
FIR07-00465
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:32:21 PM | A | NR |
|
|
Project is not ready for final due to construction underway, audible building alarm notification devices tested okay.
|
FIR07-00466
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:30:42 PM | A | NR |
|
|
Bags at SD's, finishes are not complete.
|
FIR07-00464
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:29:51 PM | A | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
FIR07-00323
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:29:17 PM | A | PASS |
|
|
Field inspection completed acceptable, permit finaled.
|
FIR07-00320
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:28:33 PM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00318
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:27:50 PM | A | PASS |
|
|
Fire alarm inspection passed, permit finaled.
|
FIR07-00648
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:27:10 PM | A | NR |
|
|
Pending completion of room finishes.
|
FIR07-00324
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:26:17 PM | A | NR |
|
|
Finishes are not complete, project is not ready for final.
|
FIR07-00332
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:25:25 PM | A | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
BLD07-00292
| FIRE-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 11:47:27 AM | A | PASS |
|
|
Fire life safety Passed.KR
|
FIR07-00243
| INSP-Sprinkler Rough-in | 1/14/2008 | 1/18/2008 | 1/18/2008 9:40:20 AM | A | PART |
|
|
First floor corridor fire sprinklers are okay for cover with the exception of two pendents in need of relocation due to overspacing from adjacent vestibules to the meeting room, also noted one head blocked by a 4' soffit at the lobby, missing head at the laundry chute termination room, discussed head location at a mech. room, the elevator pit head is not yet installed, missing escutcheons at some locations.
|