Inspections for the day of: Friday, January 18, 2008.
Number of inspections: 25
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01020 BLD-Aging Inspection1/18/20081/18/20081/24/2008 1:51:54 PMPDEFR
Inspection scheduled.
BLD03-02347 BLD-Aging Inspection1/18/20081/18/20081/23/2008 2:58:17 PMPDONE
Site inspection scheduled.
BLD07-02703 FIRE-Final Inspection1/17/20081/18/20081/18/2008 4:17:31 PMPPASS
Fire life safety passed, fire alarm modifications indicated on the permit application are not required and have not been installed-no FA permit issued due to no modifications made.
BLD07-02703 FIRE-Alarm Testing1/17/20081/18/20081/18/2008 4:14:07 PMPDONE
Not applicable to this project.
FIR07-00815 INSP-Final Inspection1/18/20081/18/20081/18/2008 4:10:56 PMPPASS
See last entry..permit Finaled. KR
FIR07-00815 FIR-Aging Inspection1/18/20081/18/20081/18/2008 3:54:31 PM PASS
This permit passed during the testing of the kitchen hood system.Connection to the main fire alarm to the kitchen suppression system was verified and tested. KR
FIR07-00593 INSP-Final Inspection1/17/20081/18/20081/18/2008 2:49:58 PMAPASS
Final passed, flow switch cover attatched while on site, tape and paper at one garage sw to be removed when painting is finished, CPVC at the riser to meet mfg. installation guidelines.
FIR07-00879 INSP-Sprinkler Rough-in1/17/20081/18/20081/18/2008 2:47:49 PMAPART
Ok to cover remaining under ground piping.
FIR07-01023 INSP-Final Inspection1/17/20081/18/20081/18/2008 2:46:29 PMPPASS
Fire sprinkler work is satisfactory, final inspection okay, permit finaled.
BLD07-02964 FIRE-Final Inspection1/17/20081/18/20081/18/2008 1:48:49 PMAPASS
No sprinkler work needed for this permit. Sprinklers were exsisting, no changes made.Life safety complete. KR
BLD08-00089 FIRE-Final Inspection1/18/20081/18/20081/18/2008 1:25:30 PMPPASS
Necessary correction completed, fire life safety inspection passed.
FIR07-01004 INSP-Final Inspection1/18/20081/18/20081/18/2008 1:24:28 PMPPASS
Required correction and system/plan modification passed inspection, permit finaled.
FIR07-00989 INSP-Final Inspection1/18/20081/18/20081/18/2008 12:56:11 PMPCANC
Overbooked, inspection rescheduled.
FIR07-00472 INSP-Final Inspection1/18/20081/18/20081/18/2008 12:37:32 PMPFAIL
Need to change descriptor for the smoke detector at the electrical closet, , damper at suite 504 did not close upon actuation of the ID detector, addresses at the in duct detectors for the shell and core devices between units 501 and 502 are not accurate (duplicated elsewhere).
FIR07-00465 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:32:21 PMANR
Project is not ready for final due to construction underway, audible building alarm notification devices tested okay.
FIR07-00466 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:30:42 PMANR
Bags at SD's, finishes are not complete.
FIR07-00464 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:29:51 PMAPASS
Fire alarm testing passed, permit finaled.
FIR07-00323 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:29:17 PMAPASS
Field inspection completed acceptable, permit finaled.
FIR07-00320 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:28:33 PMAPASS
Fire alarm permit finaled.
FIR07-00318 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:27:50 PMAPASS
Fire alarm inspection passed, permit finaled.
FIR07-00648 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:27:10 PMANR
Pending completion of room finishes.
FIR07-00324 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:26:17 PMANR
Finishes are not complete, project is not ready for final.
FIR07-00332 INSP-Final Inspection1/17/20081/18/20081/18/2008 12:25:25 PMAPASS
Fire alarm work passed inspection, permit finaled.
BLD07-00292 FIRE-Final Inspection1/17/20081/18/20081/18/2008 11:47:27 AMAPASS
Fire life safety Passed.KR
FIR07-00243 INSP-Sprinkler Rough-in1/14/20081/18/20081/18/2008 9:40:20 AMAPART
First floor corridor fire sprinklers are okay for cover with the exception of two pendents in need of relocation due to overspacing from adjacent vestibules to the meeting room, also noted one head blocked by a 4' soffit at the lobby, missing head at the laundry chute termination room, discussed head location at a mech. room, the elevator pit head is not yet installed, missing escutcheons at some locations.