FIR07-00874
| INSP-Sprinkler Rough-in | 1/15/2008 | 1/18/2008 | 1/18/2008 4:39:29 PM | P | PART |
|
|
The attic system rough-in in the south wing is passed. Per jim and I's discussion it will be ok to provide a 1" drain from the 2 1/2" branchline to the 4" main. Through bolts are required on all of the earthquake attachments. The dry piping in the overbuilds has not been installed yet nor has the 4" tie in.
|
BLD07-03062
| FIRE-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 4:37:25 PM | P | FAIL |
|
|
provide sticker at main exit as discussed, install all ceiling tile, remove the hooks off of the rear exit door and repair or remove the non functional emergency light.
|
BLD07-02601
| FIRE-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 2:54:15 PM | A | PASS |
|
|
Life safety passed.
|
BLD07-03081
| FIRE-Conference | 1/17/2008 | 1/18/2008 | 1/18/2008 2:53:00 PM | A | DONE |
|
|
I went over fire extinguisher requirements with the superintendant
|
FIR08-00020
| INSP-Sprinkler Rough-in | 1/17/2008 | 1/18/2008 | 1/18/2008 1:06:03 PM | A | PASS |
|
|
sprinkler piping is ok to cover
|
BLD07-02650
| FIRE-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 12:05:51 PM | A | PASS |
|
|
Life safety passed.
|
FIR07-00945
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 11:52:07 AM | A | PASS |
|
|
permit finaled
|
BLD08-00090
| FIRE-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 10:41:55 AM | A | FAIL |
|
|
The building has three hood systems that are out of compliance. They need to be replaced or serviced. K Class extinguisher needs to be installed. panic hardware is required at emergency side exit door due to occupancy loads.Egress light needs to be installed, noted in red on city approved plans.
|
FIR07-00945
| INSP-Alarm Testing | 1/17/2008 | 1/18/2008 | 1/18/2008 10:33:44 AM | A | DONE |
|
|
Fire alarm is non applicable
|
BLD07-00274
| FIRE-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 9:58:31 AM | A | PASS |
|
|
Life safety passed
|
FIR07-00686
| INSP-Final Inspection | 1/18/2008 | 1/18/2008 | 1/18/2008 9:57:55 AM | P | PASS |
|
|
permit finaled
|
FIR08-00028
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 8:54:23 AM | A | PASS |
|
|
permit finaled
|
FIR07-01006
| INSP-Final Inspection | 1/17/2008 | 1/18/2008 | 1/18/2008 8:48:32 AM | A | PASS |
|
|
the hood suppression system operated correctly
|