Inspections for the day of: Friday, January 18, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00874 INSP-Sprinkler Rough-in1/15/20081/18/20081/18/2008 4:39:29 PMPPART
The attic system rough-in in the south wing is passed. Per jim and I's discussion it will be ok to provide a 1" drain from the 2 1/2" branchline to the 4" main. Through bolts are required on all of the earthquake attachments. The dry piping in the overbuilds has not been installed yet nor has the 4" tie in.
BLD07-03062 FIRE-Final Inspection1/18/20081/18/20081/18/2008 4:37:25 PMPFAIL
provide sticker at main exit as discussed, install all ceiling tile, remove the hooks off of the rear exit door and repair or remove the non functional emergency light.
BLD07-02601 FIRE-Final Inspection1/17/20081/18/20081/18/2008 2:54:15 PMAPASS
Life safety passed.
BLD07-03081 FIRE-Conference1/17/20081/18/20081/18/2008 2:53:00 PMADONE
I went over fire extinguisher requirements with the superintendant
FIR08-00020 INSP-Sprinkler Rough-in1/17/20081/18/20081/18/2008 1:06:03 PMAPASS
sprinkler piping is ok to cover
BLD07-02650 FIRE-Final Inspection1/17/20081/18/20081/18/2008 12:05:51 PMAPASS
Life safety passed.
FIR07-00945 INSP-Final Inspection1/17/20081/18/20081/18/2008 11:52:07 AMAPASS
permit finaled
BLD08-00090 FIRE-Final Inspection1/17/20081/18/20081/18/2008 10:41:55 AMAFAIL
The building has three hood systems that are out of compliance. They need to be replaced or serviced. K Class extinguisher needs to be installed. panic hardware is required at emergency side exit door due to occupancy loads.Egress light needs to be installed, noted in red on city approved plans.
FIR07-00945 INSP-Alarm Testing1/17/20081/18/20081/18/2008 10:33:44 AMADONE
Fire alarm is non applicable
BLD07-00274 FIRE-Final Inspection1/17/20081/18/20081/18/2008 9:58:31 AMAPASS
Life safety passed
FIR07-00686 INSP-Final Inspection1/18/20081/18/20081/18/2008 9:57:55 AMPPASS
permit finaled
FIR08-00028 INSP-Final Inspection1/17/20081/18/20081/18/2008 8:54:23 AMAPASS
permit finaled
FIR07-01006 INSP-Final Inspection1/17/20081/18/20081/18/2008 8:48:32 AMAPASS
the hood suppression system operated correctly