Inspections for the day of: Wednesday, January 18, 2012.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02918 FIRE-Final Inspection1/17/20121/18/20121/20/2012 11:30:19 AMAPASS
Fire life safety inspection passed.
BLD11-02919 FIRE-Final Inspection1/17/20121/18/20121/20/2012 11:28:58 AMAFAIL
Provide exit signage and PFE per plan, noted new VESDA at the laser lab, discussed discernable exit path.
FIR11-00483 INSP-Sprinkler Rough-in1/17/20121/18/20121/18/2012 6:05:11 PMPPART
Rough-in inspection completed. Noted items include obstructed upright coverage at the 1st and 2nd floors at some locations due to ductwork, adjacent truss webs, etc. Verified previous c/n items.
BLD11-01845 FIRE-Final Inspection1/18/20121/18/20121/18/2012 5:52:01 PMPPASS
Fire life safety finaled.
FIR11-00542 INSP-Final Inspection1/18/20121/18/20121/18/2012 5:51:06 PMPPASS
Fire sprinkler work passed final inspection.
BLD11-03038 FIRE-Final Inspection1/13/20121/18/20121/18/2012 5:49:30 PMAFAIL
Noted items include; provide approved hardware and "door to remain.." signage at the main entry, repair one EM light, provide approved hardware at the restroom. Note* A portion of this structure appears to be used as a residence- mixed use is not indicated in the permit documents or plan review notes.