PLM17-00057
| Final | 1/10/2017 | 1/11/2017 | | A | |
|
|
Phone #: ###-#### >> Inspection requested via web by Boe Jares
|
PLM15-03307
| PLM-Aging Inspection | 1/18/2017 | 1/18/2017 | 1/25/2017 11:50:37 AM | | PEND |
|
|
Spoke to the homeowner and contractor. Contractor to schedule
|
PLM16-02305
| PLM-Aging Inspection | 1/18/2017 | 1/18/2017 | 1/19/2017 10:55:37 AM | | PASS |
|
|
Ran to an area approved by Jim per Contractor
|
PLM17-00111
| Final | 1/18/2017 | 1/18/2017 | 1/18/2017 2:24:01 PM | P | PASS |
|
|
Would like call when on way. thank you! Phone #: ###-#### Inspection requested via web by Xanti Berria 20# test ok
|
PLM17-00064
| Plumbing Rough-in | 1/17/2017 | 1/18/2017 | 1/18/2017 12:20:00 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Branden Steers
|
PLM17-00103
| Water and/or Sewer | 1/17/2017 | 1/18/2017 | 1/18/2017 12:13:21 PM | A | FAIL |
|
|
victor Phone #: ###-#### 1. Install a tracer wire on the water service per ISPC 604.8. 2. Test the water service with 50 psi air or water. 3. Test the sewer with 5 psi air pressure or fill with water. 4. Install Schedule 40 pipe 3 feet from the house into the crawl space. 5. Install a schedule 40 wye branch fitting for the sewer cleanout. A santiary tee is not acceptable. 6. The gasketed 3034 sewer pipe is installed backwards. The female hub must be downstream of the male pipe. See drawing on the correction notice.
|
PLM17-00060
| Water and/or Sewer | 1/16/2017 | 1/18/2017 | 1/18/2017 11:00:12 AM | A | PASS |
|
|
Can we schedule a conference to discuss a few questions please? I am available on Wed any time. Thank you for your time. Aaron Johnson Phone #: ###-#### Inspection requested via web by Sarah Johnson
|