Inspections for the day of: Friday, January 18, 2019.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02816 Conference1/18/20191/18/20191/18/2019 3:41:27 PMPPASS
Need inspection for bringing existing building up to code. Phone #: ###-#### Inspection requested via web by Kotton Corder...
walked job with journeyman on site
discussed work done and current code violations still existing
Building wiring shall be wired as Class II Division I codes
ELE18-04697 Rough-In Permanent Service1/18/20191/18/20191/18/2019 2:19:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Krista Ratterree....
service switch gear and grounding installed by others
underground and wire feeds done by contractor
p/s u/g new ok
ELE19-00173 Permanent Service1/15/20191/18/20191/18/2019 1:40:02 PMPPASS
This work has been coordinated with Idaho Power to disconnect power at 9am. Work will be completed and ready to inspect by early afternoon 1-2. Please contact Tyson to coordinate a time to inspect this panel upgrade so we can restore power to the residence in a timely manner. Phone #: ###-#### Inspection requested via web by Tyson Dye...
p/s reconnect ok
ELE19-00158 Final1/18/20191/18/20191/18/2019 1:13:30 PMPPASS
Phone #: ###-#### Inspection requested via web by Matthew White...
outlet added in ceiling for pool table light
ok to final
ELE19-00187 Final1/18/20191/18/20191/18/2019 12:23:48 PMPPASS
final for TV cabinet...no further inspections needed...ok to final
ELE19-00186 Final1/18/20191/18/20191/18/2019 12:23:14 PMPPASS
final for TV cabinet...no further inspections needed...ok to final
ELE19-00222 Final1/18/20191/18/20191/18/2019 12:19:52 PMPPASS
final and permanent service for cable t v power supply .located at s e corner of 3021 n ash park ln .contact #2088694390 Andy. Phone #: ###-#### Inspection requested via web by andrew dopieralski...
no other inspection needed...ok to final
ELE19-00222 Rough-In Permanent Service1/18/20191/18/20191/18/2019 12:19:24 PMPPASS
final and permanent service for cable t v power supply .located at s e corner of 3021 n ash park ln .contact #2088694390 Andy. Phone #: ###-#### Inspection requested via web by andrew dopieralski....
p/s u/g new ok
ELE18-04660 Final1/17/20191/18/20191/18/2019 11:46:54 AMAPART
Partial Final Phone #: ###-#### Inspection requested via web by Kerri Hamilton...
partial to give temp occupency to move furniture in but no business to take place
remaining...all cubicles installed and power hooked up, missing blank, power to 2 offices outlets
ELE18-03046 Final1/17/20191/18/20191/18/2019 11:11:52 AMAPASS
Please call an hour in advance to have homeowner let inspector in // Mike Phone #: ###-####...ok to final
ELE18-04697 Final1/17/20191/18/20191/18/2019 10:16:09 AMAFAIL
Rhonda Phone #: ###-####...
no rough inspection was performed on service or work...unable to verify grounding at service, generator, and transformer...AFC label needs applied to service...a rough permanent service inspection is required before a final can be scheduled
ELE19-00046 Final1/17/20191/18/20191/18/2019 9:59:23 AMAPASS
Adam Jr Phone #: ###-####...
labelling, disconnect, and OCPD
ok to final
ELE19-00217 Final1/17/20191/18/20191/18/2019 9:42:43 AMACANC
Phone #: ###-#### Inspection requested via web by Don Conley....
final can not be done until power is restored to space and work complete
ELE19-00217 Permanent Service1/17/20191/18/20191/18/2019 9:41:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Don Conley....
power off for over yr
p/s u/g reconnect ok
ELE19-00208 Final1/17/20191/18/20191/18/2019 9:12:46 AMAPASS
installed outlet for gas range. Tenant home in morning. Jason is our contact.
Thank You! Phone #: ###-#### Inspection requested via web by Kelly Felin...
use of existing 240v circuit to 2 110 circuits...
ok to final
ELE19-00197 Temporary Service1/17/20191/18/20191/18/2019 8:57:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Dean Gernaat...
t/s u/g new ok
ELE19-00204 Temporary Service1/17/20191/18/20191/18/2019 8:16:56 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn....
1...1 ground rod shall be driven for temp service
2..service ground shall be installed to ground rod
ELE19-00198 Rough-In Permanent Service1/17/20191/18/20191/18/2019 8:15:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt...
rough ok to cover
p/s u/g new ok
ELE18-04183 Electrical Rough-In1/11/20191/18/20191/15/2019 3:24:08 PMACANC
Phone #: ###-#### >> Inspection requested via web by Laurie Hoelscher Inspection cancelled from web by: Laurie Hoelscher