Inspections for the day of: Friday, January 19, 1996.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE96-00140 INSP - T/S and Final1/19/19961/19/19961/22/1996 12:00:00 AMPPASS
01/19/96 336 - REINSPECTION T/S Ok final Ok
ELE96-00175 INSP - Electrical Rough-In1/19/19961/19/19961/22/1996 12:00:00 AMPPASS
01/19/96 336 - REINSPECTION R/I disapproved circuiting and ceiling rated boxes
ELE96-00205 INSP - Ele Rough-In/Perm Svc1/19/19961/19/19961/22/1996 12:00:00 AMPPASS
01/19/96 336 - 14 ROOMS AC 200 AMPS P/S & R/I Ok
ELE96-00208 INSP - Electrical Rough-In1/19/19961/19/19961/22/1996 12:00:00 AMPPASS
01/19/96 336 - THIS IS FOR LATE PM. SERVICE UPGRADE REMODEL OF 2 ROOMS Ok
ELE95-02290 INSP - Final1/18/19961/19/19961/19/1996 12:00:00 AMAPASS
01/18/96 336 - final Ok
ELE96-00068 INSP - Conference1/18/19961/19/19961/19/1996 12:00:00 AMAPASS
01/18/96 336 - CONF. ok
ELE96-00200 INSP - Permanent service1/18/19961/19/19961/19/1996 12:00:00 AMAPASS
01/19/96 336 - THIS IS FOR A MOBILE HOME P/S O/H Ok
ELE2057346 INSP - Electrical Rough-In1/18/19961/19/19961/19/1996 12:00:00 AMAPASS
01/19/96 336 - 2ND FLOOR COLUMN 3RD FLOOR CENTRAL CORE Partial R/I Ok
ELE95-01552 INSP - Ground work1/18/19961/19/19961/19/1996 12:00:00 AMAPASS
01/19/96 336 - THEY WOULD LIKE THIS IN THE AM Ok
ELE95-01997 INSP - Electrical Rough-In1/18/19961/19/19961/19/1996 12:00:00 AMAPASS
01/18/96 336 - THIS IS FOR A CEILING INSPECTION Partial R/I ok
ELE95-02046 INSP - Final1/19/19961/19/19961/19/1996 12:00:00 AMPFAIL
01/19/96 336 - GO TO COLOR TILE IN THE FRONT DOOR.. Final disapproved posted correction ground receps in raised covers and lock-out for signs
ELE95-00620 INSP - Electrical Rough-In1/16/19961/19/19961/19/1996 12:00:00 AMPCANC
01/18/96 336 - SCHEDULED FOR FRIDAY AT 1:30--2 ROOMS Gave to Jack
ELE96-00181 INSP - Permanent service1/19/19961/19/19961/19/1996 12:00:00 AMPPASS
01/19/96 336 - REINSPECTION P/S Ok
ELE96-00198 INSP - Low voltage wiring1/19/19961/19/19961/19/1996 12:00:00 AMPNR
01/19/96 336 - Not ready for final .
ELE96-00201 INSP - Electrical Rough-In1/18/19961/19/19961/19/1996 12:00:00 AMPFAIL
01/19/96 336 - ADDING 1 CIRCUIT, ASK FOR CHAUNCEY R/I disapproved posted correction mc cable not supported or terminated i fittings recep in raised cover not held with two screws.