BLD04-00640
| FIRE-Final Inspection | 1/19/2006 | 1/19/2006 | 1/19/2006 4:57:56 PM | P | FAIL |
|
|
Per Sam Rogers a temporary occupancy can be given if the elevators get signed off by the state elevator inspectors. This temporary occupancy is good for the fire alarm permit as well.
|
FIR05-00104
| INSP-Alarm Testing | 1/19/2006 | 1/19/2006 | 1/19/2006 4:56:54 PM | P | FAIL |
|
|
Need to install weather proof backboxes in the pool area and provide correct sample tubes lenghts in the duct smoke detectors. Still waiting on approved resubmitted plans for the fire alarm. Per Sam Rogers a temporary occupancy can be given if the elevators get signed off by the state elevator inspectors.
|
BLD05-01694
| FIRE-Final Inspection | 1/17/2006 | 1/19/2006 | 1/19/2006 4:53:51 PM | A | FAIL |
|
|
Insulation is falling from the roof deck and obstructing the upright sprinkler heads. The sprinkler heads along the north wall are overspaced from the north wall and plywood attached to the bottom of the joists at the east wall create obstructions.
|
BLD05-02887
| FIRE-Final Inspection | 1/19/2006 | 1/19/2006 | 1/19/2006 2:00:46 PM | P | PASS |
|
|
fire life safety finaled
|
FIR05-00312
| INSP-Sprinkler Rough-in | 1/17/2006 | 1/19/2006 | 1/19/2006 12:31:30 PM | A | PART |
|
|
The south wing piping in the attic area is ok to cover with insulation
|
BLD05-03322
| FIRE-Conference | 1/19/2006 | 1/19/2006 | 1/19/2006 12:30:24 PM | P | DONE |
|
|
brandon ; Phone #: ###-#### Met and discussed exit signs/emergency lights. I'm ok with deleting two of the four exit signs/emergency lights in the storage area. The occupant load is only four people for this area.
|
BLD05-03089
| FIRE-Final Inspection | 1/18/2006 | 1/19/2006 | 1/19/2006 11:40:47 AM | A | PASS |
|
|
Life safety finaled
|
BLD05-02583
| FIRE-Final Inspection | 1/18/2006 | 1/19/2006 | 1/19/2006 11:09:58 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD04-01188
| FIRE-Final Inspection | 1/18/2006 | 1/19/2006 | 1/19/2006 10:05:25 AM | A | PART |
|
|
A temporary occupancy was given with dave hanniman's permission. The two roll down fire doors are to remain closed until their operation is worked out. Provide "Fire Doors Do Not Obstruct"signs at both doors and provide occupant load signs for the three assembly areas.
|
FIR05-00068
| INSP-Final Inspection | 1/18/2006 | 1/19/2006 | 1/19/2006 10:02:19 AM | A | PASS |
|
|
Sprinkler permit finaled
|
FIR05-00108
| INSP-Final Inspection | 1/18/2006 | 1/19/2006 | 1/19/2006 10:01:39 AM | A | PASS |
|
|
Fire alarm permit finaled
|
FIR04-00619
| INSP-Final Inspection | 1/18/2006 | 1/19/2006 | 1/19/2006 8:16:30 AM | A | PASS |
|
|
permit finaled
|