Inspections for the day of: Thursday, January 19, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00640 FIRE-Final Inspection1/19/20061/19/20061/19/2006 4:57:56 PMPFAIL
Per Sam Rogers a temporary occupancy can be given if the elevators get signed off by the state elevator inspectors. This temporary occupancy is good for the fire alarm permit as well.
FIR05-00104 INSP-Alarm Testing1/19/20061/19/20061/19/2006 4:56:54 PMPFAIL
Need to install weather proof backboxes in the pool area and provide correct sample tubes lenghts in the duct smoke detectors. Still waiting on approved resubmitted plans for the fire alarm. Per Sam Rogers a temporary occupancy can be given if the elevators get signed off by the state elevator inspectors.
BLD05-01694 FIRE-Final Inspection1/17/20061/19/20061/19/2006 4:53:51 PMAFAIL
Insulation is falling from the roof deck and obstructing the upright sprinkler heads. The sprinkler heads along the north wall are overspaced from the north wall and plywood attached to the bottom of the joists at the east wall create obstructions.
BLD05-02887 FIRE-Final Inspection1/19/20061/19/20061/19/2006 2:00:46 PMPPASS
fire life safety finaled
FIR05-00312 INSP-Sprinkler Rough-in1/17/20061/19/20061/19/2006 12:31:30 PMAPART
The south wing piping in the attic area is ok to cover with insulation
BLD05-03322 FIRE-Conference1/19/20061/19/20061/19/2006 12:30:24 PMPDONE
brandon ; Phone #: ###-####
Met and discussed exit signs/emergency lights. I'm ok with deleting two of the four exit signs/emergency lights in the storage area. The occupant load is only four people for this area.
BLD05-03089 FIRE-Final Inspection1/18/20061/19/20061/19/2006 11:40:47 AMAPASS
Life safety finaled
BLD05-02583 FIRE-Final Inspection1/18/20061/19/20061/19/2006 11:09:58 AMAPASS
Fire life safety finaled
BLD04-01188 FIRE-Final Inspection1/18/20061/19/20061/19/2006 10:05:25 AMAPART
A temporary occupancy was given with dave hanniman's permission. The two roll down fire doors are to remain closed until their operation is worked out. Provide "Fire Doors Do Not Obstruct"signs at both doors and provide occupant load signs for the three assembly areas.
FIR05-00068 INSP-Final Inspection1/18/20061/19/20061/19/2006 10:02:19 AMAPASS
Sprinkler permit finaled
FIR05-00108 INSP-Final Inspection1/18/20061/19/20061/19/2006 10:01:39 AMAPASS
Fire alarm permit finaled
FIR04-00619 INSP-Final Inspection1/18/20061/19/20061/19/2006 8:16:30 AMAPASS
permit finaled