Inspections for the day of: Friday, January 19, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00720 FIR-Aging Inspection1/19/20071/19/20071/26/2007 2:54:44 PM NR
work is in progress
FIR06-00582 FIR-Aging Inspection1/19/20071/19/20071/23/2007 12:47:38 PMAFAIL
See entry dated 1/23/07 which still requires a map for the facp
FIR06-00698 INSP-Sprinkler Rough-in1/17/20071/19/20071/19/2007 4:30:05 PMPPART
I inspected the second floor dorm rooms. The upright line located in the peak needs the deflectors positioned horizontal. Also this same line needs to be positioned in the 12" box as detailed in NFPA 13. There is a combustible concealed space that encloses a chimney that will need protection. All of the other lines are ok.
FIR05-00800 INSP-Final Inspection1/18/20071/19/20071/19/2007 4:19:01 PMPFAIL
Need as-builts and the existing door holders connected to the corridor smoke detectors and shown on the as builts
BLD05-02073 FIRE-Final Inspection1/19/20071/19/20071/19/2007 4:17:47 PMPFAIL
Need fire alarm and fire sprinkler finaled first.
BLD05-01063 FIRE-Final Inspection1/19/20071/19/20071/19/2007 4:16:57 PMPFAIL
Need fire alarm and fire sprinkler finaled first.
FIR06-00977 INSP-Sprinkler Rough-in/Hydro1/18/20071/19/20071/19/2007 4:16:07 PMACANC
contractor is not ready for inspection
BLD06-01295 FIRE-Final Inspection1/18/20071/19/20071/19/2007 10:32:14 AMAFAIL
Need approved door hardware. Other items are ok.
BLD06-01601 FIRE-Final Inspection1/18/20071/19/20071/19/2007 10:31:13 AMAPART
A temporary occupancy was given until the fire dept. access curb painting is complete. All other life safety items are ok.