FIR06-00720
| FIR-Aging Inspection | 1/19/2007 | 1/19/2007 | 1/26/2007 2:54:44 PM | | NR |
|
|
work is in progress
|
FIR06-00582
| FIR-Aging Inspection | 1/19/2007 | 1/19/2007 | 1/23/2007 12:47:38 PM | A | FAIL |
|
|
See entry dated 1/23/07 which still requires a map for the facp
|
FIR06-00698
| INSP-Sprinkler Rough-in | 1/17/2007 | 1/19/2007 | 1/19/2007 4:30:05 PM | P | PART |
|
|
I inspected the second floor dorm rooms. The upright line located in the peak needs the deflectors positioned horizontal. Also this same line needs to be positioned in the 12" box as detailed in NFPA 13. There is a combustible concealed space that encloses a chimney that will need protection. All of the other lines are ok.
|
FIR05-00800
| INSP-Final Inspection | 1/18/2007 | 1/19/2007 | 1/19/2007 4:19:01 PM | P | FAIL |
|
|
Need as-builts and the existing door holders connected to the corridor smoke detectors and shown on the as builts
|
BLD05-02073
| FIRE-Final Inspection | 1/19/2007 | 1/19/2007 | 1/19/2007 4:17:47 PM | P | FAIL |
|
|
Need fire alarm and fire sprinkler finaled first.
|
BLD05-01063
| FIRE-Final Inspection | 1/19/2007 | 1/19/2007 | 1/19/2007 4:16:57 PM | P | FAIL |
|
|
Need fire alarm and fire sprinkler finaled first.
|
FIR06-00977
| INSP-Sprinkler Rough-in/Hydro | 1/18/2007 | 1/19/2007 | 1/19/2007 4:16:07 PM | A | CANC |
|
|
contractor is not ready for inspection
|
BLD06-01295
| FIRE-Final Inspection | 1/18/2007 | 1/19/2007 | 1/19/2007 10:32:14 AM | A | FAIL |
|
|
Need approved door hardware. Other items are ok.
|
BLD06-01601
| FIRE-Final Inspection | 1/18/2007 | 1/19/2007 | 1/19/2007 10:31:13 AM | A | PART |
|
|
A temporary occupancy was given until the fire dept. access curb painting is complete. All other life safety items are ok.
|