Inspections for the day of: Tuesday, January 19, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-02003 FIRE-Final Inspection1/19/20101/19/20101/20/2010 5:42:00 PMPNR
Pending project related fire alarm permit.
BLD09-01803 BLD-Aging Inspection1/19/20101/19/20101/20/2010 5:40:39 PMPDONE
Work in progress, construction underway.
FIR09-00721 INSP-Final Inspection1/19/20101/19/20101/19/2010 2:24:52 PMPFAIL
Missing drop ceiling grid and tile at one re-installed head to the east, new equipment install has created an obstructed space behind the new ice machine lacking sprinkler coverage at both the floor and above ceiling areas.
BLD09-02206 FIRE-Final Inspection1/19/20101/19/20101/19/2010 2:18:55 PMAFAIL
Final pending one exit sign and one EM light per approved plans and building code review notes at the "server room 205". See plan annotations for details. Remainder of the scope of permit work passed field inspection.
FIR09-00684 INSP-Final Inspection1/19/20101/19/20101/19/2010 2:15:44 PMPNR
Need to remove tape and paper covering upright sprinklers at all locations, missing escutcheon and finishes throughout.
BLD09-01578 FIRE-Final Inspection1/19/20101/19/20101/19/2010 2:08:57 PMAPART
Okay to apply IFC 2006 section 1008.1.8.3 (2) at the north exit door per agreement with the owner, structural and fire inspectors.
BLD09-00616 FIRE-Final Inspection1/19/20101/19/20101/19/2010 2:01:42 PMAPASS
Fire life safety passed.
BLD09-02247 FIRE-Final Inspection1/15/20101/19/20101/19/2010 12:00:00 AMACANC
jock - please call 1/2 hr prior Phone #: ###-####