BLD09-02003
| FIRE-Final Inspection | 1/19/2010 | 1/19/2010 | 1/20/2010 5:42:00 PM | P | NR |
|
|
Pending project related fire alarm permit.
|
BLD09-01803
| BLD-Aging Inspection | 1/19/2010 | 1/19/2010 | 1/20/2010 5:40:39 PM | P | DONE |
|
|
Work in progress, construction underway.
|
FIR09-00721
| INSP-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 2:24:52 PM | P | FAIL |
|
|
Missing drop ceiling grid and tile at one re-installed head to the east, new equipment install has created an obstructed space behind the new ice machine lacking sprinkler coverage at both the floor and above ceiling areas.
|
BLD09-02206
| FIRE-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 2:18:55 PM | A | FAIL |
|
|
Final pending one exit sign and one EM light per approved plans and building code review notes at the "server room 205". See plan annotations for details. Remainder of the scope of permit work passed field inspection.
|
FIR09-00684
| INSP-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 2:15:44 PM | P | NR |
|
|
Need to remove tape and paper covering upright sprinklers at all locations, missing escutcheon and finishes throughout.
|
BLD09-01578
| FIRE-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 2:08:57 PM | A | PART |
|
|
Okay to apply IFC 2006 section 1008.1.8.3 (2) at the north exit door per agreement with the owner, structural and fire inspectors.
|
BLD09-00616
| FIRE-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 2:01:42 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD09-02247
| FIRE-Final Inspection | 1/15/2010 | 1/19/2010 | 1/19/2010 12:00:00 AM | A | CANC |
|
|
jock - please call 1/2 hr prior Phone #: ###-####
|