BLD09-02162
| FIRE-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 3:57:41 PM | P | FAIL |
|
|
The exit light at the main exit did not function and the four exit lights in the two conference rooms did not function either. Emergency lighting is missing in the two conference rooms as well.
|
BLD09-00776
| FIRE-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 3:13:18 PM | P | FAIL |
|
|
An indicator has not been provided for the keyed hardware at the tenant space exit.
|
BLD08-01426
| FIRE-Final Inspection | 1/15/2010 | 1/19/2010 | 1/19/2010 3:11:55 PM | A | FAIL |
|
|
Repair the exit sign located over the main exit. Provide exit discharge lighting as shown on the approved plans at both the front and rear exits. I tried to verify the exit discharge requirement since the occupant load was only 12 but Ron Hill was unavailable so I contacted DC Engineering and spoke to Johnathan. He stated that he thought the exit discharge lighting was required.
|
BLD09-01947
| FIRE-Final Inspection | 1/19/2010 | 1/19/2010 | 1/19/2010 1:39:51 PM | P | PASS |
|
|
Life safety passed
|
BLD09-00945
| FIRE-Final Inspection | 1/18/2010 | 1/19/2010 | 1/19/2010 9:22:52 AM | A | PART |
|
|
The life safety inspection for the main lobby/waiting area remodel of Phase 6 is passed. HC Company will repair the exit sign over the main exit doors, provide an additional emergency light in the rear corridor and provide one additional fire extinguisher as discussed. These items will be verified when the remaining rooms in the lobby/waiting area are completed.
|
BLD09-01838
| FIRE-Final Inspection | 1/15/2010 | 1/19/2010 | 1/19/2010 9:13:06 AM | A | PASS |
|
|
Fire life safety passed
|