Inspections for the day of: Wednesday, January 19, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00867 FIRE-Final Inspection1/18/20111/19/20111/21/2011 2:06:26 PMAFAIL
The storage height for the sprinkler design has been exceeded. Chris is going to make adjustments and institute a height monitoring system for the rack storage. A re-inspection has been set up for next tuesday.
FIR10-00657 INSP-Final Inspection1/19/20111/19/20111/19/2011 3:46:22 PMPPASS
Permit finaled.
FIR10-00525 INSP-Final Inspection1/18/20111/19/20111/19/2011 3:40:05 PMAFAIL
Many of the sprinkler pendants are obstructed by the light fixtures. Per the residential obstruction chart a minimum distance of 3' is needed.
FIR10-00619 INSP-Final Inspection1/18/20111/19/20111/19/2011 3:20:53 PMAFAIL
The only item tested and passed was the smoke detector located in the elevator machine room. The heat detectors did not shunt. The test was stopped at this point. No other items were tested.
FIR10-00180 INSP-Final Inspection1/17/20111/19/20111/19/2011 12:42:01 PMAPASS
Permit finaled.