BLD05-00867
| FIRE-Final Inspection | 1/18/2011 | 1/19/2011 | 1/21/2011 2:06:26 PM | A | FAIL |
|
|
The storage height for the sprinkler design has been exceeded. Chris is going to make adjustments and institute a height monitoring system for the rack storage. A re-inspection has been set up for next tuesday.
|
FIR10-00657
| INSP-Final Inspection | 1/19/2011 | 1/19/2011 | 1/19/2011 3:46:22 PM | P | PASS |
|
|
Permit finaled.
|
FIR10-00525
| INSP-Final Inspection | 1/18/2011 | 1/19/2011 | 1/19/2011 3:40:05 PM | A | FAIL |
|
|
Many of the sprinkler pendants are obstructed by the light fixtures. Per the residential obstruction chart a minimum distance of 3' is needed.
|
FIR10-00619
| INSP-Final Inspection | 1/18/2011 | 1/19/2011 | 1/19/2011 3:20:53 PM | A | FAIL |
|
|
The only item tested and passed was the smoke detector located in the elevator machine room. The heat detectors did not shunt. The test was stopped at this point. No other items were tested.
|
FIR10-00180
| INSP-Final Inspection | 1/17/2011 | 1/19/2011 | 1/19/2011 12:42:01 PM | A | PASS |
|
|
Permit finaled.
|