Inspections for the day of: Thursday, January 19, 2012.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00483 INSP-Sprinkler Rough-in1/19/20121/19/20121/24/2012 7:23:29 AMPPART
FIR11-00641 INSP-Sprinkler Rough-in1/19/20121/19/20121/20/2012 10:59:27 AMPDEFR
John Phone #: ###-####
FIR11-00365 INSP-Sprinkler Rough-in1/18/20121/19/20121/20/2012 10:59:03 AMAFAIL
Rough-in inspection for system 8 sub-fab mechanical continued. Field inspection concluded prior to a complete review due to the high number of deficiencies noted which include; spacing at upright heads up to 150ft2, one sprinkler inside a sheetrock wall, upright sprinkler deflectors throughout at the deck level are not in compliance with location criteria per NFPA 13 8.6.4.1.2, missing and overspaced coverage at the end of the sub-floor link branch line, missing retainers at several beam clamps for hangers on the 3" main to the in duct sprinklers, noted sprigs at one branch line out of axis, areas below ducts over 4' at some locations are unprotected or overspaced, coverage at all areas needs to meet obstruction guidelines per NFPA 13 8.6.5.2 and 8.6.5.3, lacking branchline restraint, unfinished install at various locations, modifications to the floorplan which are not protected or accounted for in the sprinkler design, etc.
FIR11-00567 INSP-Conference1/18/20121/19/20121/19/2012 11:04:43 AMADONE
On site conference regarding location of the FACP and the MP station at the riser room to comply with NFPA 72 and NEC clearance and access guidelines.
BLD07-03014 FIRE-Final Inspection1/18/20121/19/20121/19/2012 9:11:50 AMAPASS
Life safety finaled.