Inspections for the day of: Tuesday, January 19, 2016.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC15-02263 Final1/19/20161/19/20161/19/2016 4:20:50 PMPPART
Ival Phone #: ###-#### Inspection requested via web by Dustin Rich everything except the kitchen exhaust hood.
MEC15-05076 Rough-in1/19/20161/19/20161/19/2016 4:20:04 PMPPART
Zack Phone #: ###-#### alan approved the wall behind the hood, he didn't do a light test on the grease duct, there is a lip at the exhaust duct that will catch grease and this system isn't in accordance with the approved plans.
MEC16-00266 Rough-in1/19/20161/19/20161/19/2016 3:43:35 PMPFAIL
Oleg Phone #: ###-#### 6" outside air to the return plenum required. you have 4" to the ceiling return grill.
GCM15-00244 GCM-Rough-in1/19/20161/19/20161/19/2016 2:28:44 PMPPASS
Arcadio ###-#### ri 20# gas 5# flue tests ok
MEC15-04934 Final1/19/20161/19/20161/19/2016 12:12:01 PMPPASS
PLM15-03662 Final1/19/20161/19/20161/19/2016 12:10:51 PMPPASS
MEC15-05735 Pressure Test1/18/20161/19/20161/19/2016 11:36:12 AMAFAIL
Phone #: ###-#### Inspection requested via web by Krista Boss does not match design
MEC15-05735 Rough-in1/18/20161/19/20161/19/2016 11:31:15 AMAFAIL
Phone #: ###-#### Inspection requested via web by Krista Boss does not match approved design
MEC16-00247 Final1/18/20161/19/20161/19/2016 10:34:40 AMAPART
We need a partial final please. Call Rick with questions. Thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum defuser replacement marked on plans ok
MEC16-00072 Rough-in1/18/20161/19/20161/19/2016 10:04:14 AMACANC
This will be a light inspection. Please call Casey Heesch the lead at the job with any further questions. ###-####. Phone #: ###-#### Inspection requested via web by Bailey Esposito wrong job called in, the building permit for this one isn't issued yet
MEC16-00115 Final1/18/20161/19/20161/19/2016 9:50:28 AMAPASS
If possible, can we have someone out about 10:30 AM tomorrow, please? Thank you! Phone #: ###-#### Inspection requested via web by Rick Borg
MEC16-00230 Final1/18/20161/19/20161/19/2016 9:24:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC16-00141 Pressure Test1/18/20161/19/20161/19/2016 9:06:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart ri 20# gas 5# flue tests ok
MEC16-00141 Rough-in1/18/20161/19/20161/19/2016 9:05:44 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart ri 20# gas 5# flue tests ok
MEC16-00143 Pressure Test1/18/20161/19/20161/19/2016 8:53:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Hart ri 20# gas 5# flue tests ok
MEC16-00086 Final1/13/20161/19/20161/19/2016 8:42:37 AMAPASS
Call to make sure homeowner remembers and to meet you thers
Thanks Phone #: ###-#### Inspection requested via web by Rene Neumeyer fp final ok
MEC16-00227 Final1/15/20161/19/20161/19/2016 8:24:42 AMAFAIL
Please contact Joel for access ###-####.
Contact Ryan with questions ###-####. Phone #: ###-#### Inspection requested via web by Lea Briggs exhaust leak, protect line set from UV
MEC15-02285 Mec-Aging Inspection1/19/20161/19/20161/19/2016 8:02:31 AM PEND
no calls
MEC15-02263 Mec-Aging Inspection1/19/20161/19/20161/19/2016 8:00:16 AM PEND
no calls
MEC15-02279 Mec-Aging Inspection1/19/20161/19/20161/19/2016 7:58:39 AM PEND
no calls