Inspections for the day of: Friday, January 2, 1998.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCarl Dependahl
TitleBLD-COM/RES INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC97-03954 INSP - Rough-in & Gas Pressure12/31/19971/2/19981/2/1998 12:00:00 AMAFAIL
C/N, NO DRYER VENT, PLENUM; NEED NEW GAGE FOR PRESS TEST.
BLD97-01825 INSP - Final12/30/19971/2/19981/2/1998 12:00:00 AMAFAIL
NEED ENGS LETTER, AIR SEAL, ETC.
BLD97-02120 INSP - Framing/Rough-in12/31/19971/2/19981/2/1998 12:00:00 AMACANC
CANC PER RITA
BLD97-02819 INSP - Energy code compliance1/5/19981/2/19981/2/1998 12:00:00 AMAPART
342 area, wall ins ok.
BLD97-03114 INSP - Carpentry1/2/19981/2/19981/2/1998 12:00:00 AMAPART
1 HR CONST AT COMMON WALLS
BLD97-03115 INSP - Carpentry1/2/19981/2/19981/2/1998 12:00:00 AMAPART
1 HR CONST
BLD97-03493 INSP - Final12/31/19971/2/19981/2/1998 12:00:00 AMAFAIL
deck\\plans are in plastic bag by door...need grippable hand rail,c/n. 340 NEVER ISSUED A HARD CARD
BLD97-03568 INSP - Framing/Rough-in12/31/19971/2/19981/2/1998 12:00:00 AMAFAIL
NEED STRAPS, TRUSS CALCS, PLBG R/I, ETC. DON'T INSUL
BLD97-03568 INSP - Energy code compliance12/31/19971/2/19981/2/1998 12:00:00 AMANR
NO INSUL, FRAME C/N
MEC97-03637 INSP - Final1/2/19981/2/19981/2/1998 12:00:00 AMPNR
need range duct completed
MEC97-03637 INSP - Final1/2/19981/2/19981/2/1998 12:00:00 AMPNR
need range duct completed
MEC97-03930 INSP - Gas pressure test1/2/19981/2/19981/2/1998 12:00:00 AMPNR
GAGE SHOWED ONLY 16-17 LBS...TALKED TO OWNER, TOLD TO RE CALL OR HAVE GAS CO. WITNESS TEST, SAID HE'D WAITED SINCE TUES. BUT TEST NOT DONE??? GAVE HIM MY CEL NO. IF HE NEEDED APPOINTMENT, BUT I COULDN'T PASS TEST AT PRESENT...
BLD97-03385 INSP - Conference1/5/19981/2/19981/2/1998 12:00:00 AMPPASS
W/ FRAMER RE: 1HR REQS
BLD97-03386 INSP - Carpentry1/5/19981/2/19981/2/1998 12:00:00 AMPPART
1HR WALL AT GARAGE
BLD97-02819 INSP - Framing/Rough-in12/31/19971/2/19981/2/1998 12:00:00 AMPPART
342 area; Insulated, c/n...need to nail off hangers, complete fireblocking & air seal, ok to cover exc. bath lid area.