Inspections for the day of: Tuesday, January 2, 2007.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00297 FIR-Aging Inspection1/2/20071/2/20071/9/2007 1:19:04 PM DONE
wip
FIR06-00595 INSP-Alarm Testing12/29/20061/2/20071/3/2007 2:41:37 PMAPART
Inspection for location, spacing, cd rating, and installation of fire alarm notification devices at the basement level only. Noted on approved plans areas which are lacking proper coverage including the break room, mech. room, transformer room, and one hallway, also noted that FA wire must be attatched to the building structure per NFPA 72, no access was provided for the womens locker area or one server room at this inspection, will require as-built drawings at the next scheduled inspection reflecting changes made.
FIR06-00674 INSP-Sprinkler Rough-in12/29/20061/2/20071/3/2007 9:28:35 AMPPART
Duplicated inspection request for the insulation at the vicinity of the tank access lid.
FIR05-00695 INSP-Alarm Testing1/2/20071/2/20071/2/2007 2:42:22 PMPFAIL
Alarm testing for the 9th floor guest rooms and common corridors only completed today. Noted the strobes are not in sync at the HC rooms 911 and 910, also noted the a/v in the 910 restroom is functional on strobe only and did not reset, dampers at two locations did not operate, the SD's in the common corridor failed to initiate a general alarm condition.
FIR06-00677 INSP-Sprinkler Rough-in/Hydro12/29/20061/2/20071/2/2007 1:01:25 PMAPART
Hydrostatic test for the added piping passed, sprinkler installation is NOT approved for cover at the kitchen area due to obstructions to discharge created by insulation batting adjacent to the upright heads.
BLD06-01968 FIRE-Final Inspection12/29/20061/2/20071/2/2007 12:13:13 PMAFAIL
Need to provide current annual certification tags for the provided fire extinguishers, missing signage above the door at the NE exit from the office area, door hardware at the pool enclosure gates is not approved.
FIR06-00870 INSP-Final Inspection12/29/20061/2/20071/2/2007 11:05:39 AMAPASS
Fire sprinkler permit finaled.
FIR06-00717 INSP-Sprinkler Rough-in/Hydro12/29/20061/2/200712/29/2006 4:31:27 PMACANC
Contact: Fred; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley