Inspections for the day of: Friday, January 2, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04503 DOC - Permit Expired1/2/20091/2/20091/2/2009 2:24:23 PMPPASS
no action ever taken on permit
ELE06-02705 DOC - Permit Expired1/2/20091/2/20091/2/2009 2:23:27 PMPPASS
no action ever taken on permit
ELE06-02768 DOC - Permit Expired1/2/20091/2/20091/2/2009 2:22:30 PMPPASS
no action ever taken on permit
ELE06-04166 DOC - Permit Expired1/2/20091/2/20091/2/2009 2:21:29 PMPPASS
no action ever taken on permit
ELE08-02952 Final1/2/20091/2/20091/2/2009 12:32:45 PMPPASS
rick Phone #: ###-#### ok card signed
ELE08-02992 Final1/1/20091/2/20091/2/2009 11:50:06 AMAFAIL
Key is above door Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called corr. B. M. C. 4-05-33 light fixtures shall be labeled and listed 210.62 show window recepts shall be not more than 18" above window, 410.62(C)(1) if cord and plug connected fixture shall be located directory below outlet, 600.5 shall provide 20 amp dedicated sign circuit, 100.26(F)(1) shall remove low voltage conduit and wiring from below panel
ELE08-01131 DOC - Permit Expired1/2/20091/2/20091/2/2009 9:44:45 AMAPASS
called contr