Inspections for the day of: Friday, January 2, 2009.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01619 FIRE-Final Inspection12/31/20081/2/20091/5/2009 11:59:23 AMAPASS
Life safety passed
FIR08-00487 INSP-Sprinkler Rough-in/Hydro12/30/20081/2/20091/2/2009 4:00:12 PMPCANC
Jeremy V is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
BLD08-02588 FIRE-Final Inspection1/2/20091/2/20091/2/2009 3:59:36 PMPPASS
Life safety passed. The 12' racks as shown on the plans have been removed. Per the contractor a separate racking permit is going to be applied for. The owner is currently moving in wooden boxes (POD's) that are roughly 7'-0" square in the building with smoke damaged furniture inside of them.
BLD08-01988 FIRE-Final Inspection1/2/20091/2/20091/2/2009 2:21:31 PMPFAIL
Provide testing of the duct smoke detectors, provide the correct remote annunciators for the duct smoke detectors, provide panic hardware for the main exit as required on the plans, provide occupant load sign and provide sticker over the door with the keyed hardware as required.