BLD08-01619
| FIRE-Final Inspection | 12/31/2008 | 1/2/2009 | 1/5/2009 11:59:23 AM | A | PASS |
|
|
Life safety passed
|
FIR08-00487
| INSP-Sprinkler Rough-in/Hydro | 12/30/2008 | 1/2/2009 | 1/2/2009 4:00:12 PM | P | CANC |
|
|
Jeremy V is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus
|
BLD08-02588
| FIRE-Final Inspection | 1/2/2009 | 1/2/2009 | 1/2/2009 3:59:36 PM | P | PASS |
|
|
Life safety passed. The 12' racks as shown on the plans have been removed. Per the contractor a separate racking permit is going to be applied for. The owner is currently moving in wooden boxes (POD's) that are roughly 7'-0" square in the building with smoke damaged furniture inside of them.
|
BLD08-01988
| FIRE-Final Inspection | 1/2/2009 | 1/2/2009 | 1/2/2009 2:21:31 PM | P | FAIL |
|
|
Provide testing of the duct smoke detectors, provide the correct remote annunciators for the duct smoke detectors, provide panic hardware for the main exit as required on the plans, provide occupant load sign and provide sticker over the door with the keyed hardware as required.
|