Inspections for the day of: Thursday, January 2, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00651 ELE-Aging Inspection1/2/20141/2/20141/7/2014 9:48:07 AM DONE
Left information on recorder about required final inspection
ELE12-00255 Final1/1/20141/2/20141/2/2014 3:50:55 PMPPASS
Please inspect at 3:30 or after, home owner can only be home then. Call 30 mins ahead. Thank You Phone #: ###-#### >> Inspection requested via web by John VanZandt job complete, final ok
ELE13-03524 Final1/2/20141/2/20141/2/2014 3:28:23 PMPFAIL
Heather-Please call prior to inspection Phone #: ###-#### NEC 310.1 Requires THNNW in be installed inside raceway for protection from physical damage. EMT and PVC conduits are require to be secured within 3 feet of connection of disconnect box.
ELE13-03577 Final1/2/20141/2/20141/2/2014 2:24:25 PMPFAIL
NEC 625.23 For electric vehicle supply equipmentrated more than 60 ampere or more than 150 volts to ground, the disconnecting means shall be provided installed in a ready accessible location. The disconnecting means shall be capable of being locked in the open position.
ELE13-03403 Electrical Rough-In1/2/20141/2/20141/2/2014 1:53:37 PMPPASS
walls & hard lids Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack rough-in ok cover walls and bathroom hard lid
ELE13-02592 Final1/1/20141/2/20141/2/2014 1:20:17 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt final ok
ELE14-00008 Final1/2/20141/2/20141/2/2014 1:15:37 PMPPASS
added a light on front awning Phone #: ###-#### >> Inspection requested via web by Danny Perrine final ok
ELE13-03413 Final1/2/20141/2/20141/2/2014 1:10:39 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Greg Idsinga final ok
ELE13-01977 Final1/2/20141/2/20141/2/2014 12:55:18 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Greg Idsinga final ok
ELE13-03556 Rough-In Permanent Service12/31/20131/2/20141/2/2014 10:16:46 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn rough-in p/s u/g n ok
ELE13-03566 Rough-In Permanent Service12/31/20131/2/20141/2/2014 9:28:26 AMAPASS
Rough in and Service Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe rough-in p/s u/g n ok
GCE13-00218 GCE-Rough-In12/31/20131/2/20141/2/2014 9:13:48 AMAPASS
David ###-#### rough-in ok cover
GCE13-00218 GCE-Permanent Service1/2/20141/2/20141/2/2014 9:13:21 AMAPASS
David ###-#### p/s u/g n ok
ELE13-03408 Final1/1/20141/2/20141/2/2014 8:49:08 AMANR
Phone #: ###-#### >> Inspection requested via web by Mark Estep Not ready for final at this time
ELE13-03408 Permanent Service1/2/20141/2/20141/2/2014 8:44:43 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Mark Estep p/s u/g rec ok
ELE13-01725 Final12/31/20131/2/20141/2/2014 8:21:02 AMAPASS
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas final ok