Inspections for the day of: Friday, January 2, 2015.
Number of inspections: 8
Percentage of inspections complete: 88 %
Percentage of inspections not complete: 13 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00344 INSP-Sprinkler Rough-in12/29/201412/30/2014 P 
Inspection for 1st floor soffits area a and b. Contact is Raul ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Carter II
FIR14-00671 INSP-Sprinkler Rough-in/Hydro12/30/20141/2/20151/2/2015 5:25:28 PMPPART
Rough-in inspection completed for new rack system sprinkler piping and modifications to existing overhead coverage. Noted one missing sprig to be added per plan note #15. Discussed 24 hr. air test.
FIR14-00936 INSP-Final Inspection12/31/20141/2/20151/2/2015 5:19:28 PMPNR
Scope of work is not yet finished.
FIR14-00481 INSP-Final Inspection12/30/20141/2/20151/2/2015 2:11:40 PMANR
Today's inspection rescheduled per contractor request. Initial site inspection completed 12/31- noted correction items included; relocate SD at elevator lobby second floor, provide missing strobe or revise cd setting at the first floor hallway SE end, PIV tamper switch adjustment, first floor flow switch adjustment, drawings to reflect field changes of deleted SD at patient rooms, deleted SD and HD at the elevator hoistway and deleted duct detectors. Monitoring and account information set up finished while on site 12/31 PM.
FIR14-00778 INSP-Sprinkler Rough-in12/30/20141/2/20151/2/2015 12:53:27 PMAPART
Completed rough-in inspection for the dry system area E third floor. Noted one missing seismic brace. A portion of framing/blocking at eaves to remain open to ensure adequate coverage.
FIR14-00708 INSP-Sprinkler Rough-in12/30/20141/2/20151/2/2015 12:49:05 PMAFAIL
Field installation does not match approved drawings. Noted changes to branchlines, number of sprinklers, and head layout compared to the design. - Inspection area wing E third floor.
BLD13-03348 FIRE-Final Inspection12/31/20141/2/20151/2/2015 12:00:00 AMPCANC
Bill ###-####
BLD13-03291 FIRE-Final Inspection12/31/20141/2/20151/2/2015 12:00:00 AMPCANC
Bill ###-####