Inspections for the day of: Wednesday, January 2, 2019.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03434 Final1/2/20191/2/20191/2/2019 2:59:07 PMPPASS
Combo for door is 2360
Thanks
Dustin Phone #: ###-#### Inspection requested via web by Dustin Kuester Final ok
ELE18-03320 Electrical Rough-In1/2/20191/2/20191/2/2019 2:35:48 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Level 3 office grid only cloud not ready rough in ok cover
ELE18-04558 Final1/2/20191/2/20191/2/2019 1:37:56 PMPFAIL
JR. Phone #: ###-#### Inspection requested via web by Sean DeLacy
IECC 405 2- Lighting controls mandatory. Occupancy sensor or manual control to reduce lighting output by 50% required.
NEC 110.3- Unable to locate emergency ballast luminaires as noted on print.
400.12 (2) and (5)- Flexible cords shall not be run through suspended ceilings or be run above suspended ceilings.
ELE18-04864 Rough-In Permanent Service12/31/20181/2/20191/2/2019 10:23:21 AMAPASS
Please let me know when done text or phone call Phone #: ###-#### Inspection requested via web by Thomas wilson
Chassis bond complete on north side.
Underground rough in ok cover p/s u/g rec ok
ELE18-04722 Electrical Rough-In12/28/20181/2/20191/2/2019 9:28:05 AMANR
Phone #: ###-#### Inspection requested via web by Lance Litchy
Will recall when ready