Inspections for the day of: Tuesday, January 20, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00620 INSP-Final Inspection1/16/20041/20/20041/20/2004 12:00:00 AMAFAIL
mark ; Phone #: ###-#### Internet Inspection Request from: Annette Moore smoke detector for FACP located too far down on wall; it will be relocated 1/20/2004 11:37:37 AM
FIR03-00070 INSP-Final Inspection1/16/20041/20/20041/20/2004 12:00:00 AMAPASS
###-#### all notification and smoke detectors within this space are on the 2 east panel; the sprinklers are still on the other building zone and plans/installation are in progress 1/20/2004 11:35:34 AM
BLD03-02876 FIRE-Final Inspection1/19/20041/20/20041/20/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 1/19/2004 at 10:54:06 AM. Contact: ###-####. not a final inspection but a conference about the alarm system; the alarm system is not required for this occupancy and the system will have to be brought up to current notification/initiation standard or the system removed; submittals are required to do either and to add the new duct detector for the new AHU 1/20/2004 3:25:20 PM
BLD03-02848 FIRE-Final Inspection1/19/20041/20/20041/20/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 1/19/2004 at 3:15:33 PM. Contact: ###-####. The fire sprinkler tamper valves are not supervised by the fire alarm panel; the GC will have them added with fire alarm submittals under BLD03-02412 1/20/2004 3:11:22 PM
BLD02-02815 FIRE-Conference1/20/20041/20/20041/20/2004 12:00:00 AMAPART
met with Jason and the sprinklers will be on the 2 east sprinkler zone for alarm notification
FIR03-00759 INSP-Final Inspection1/20/20041/20/20041/20/2004 12:00:00 AMPPASS
BLD03-02412 FIRE-Conference1/20/20041/20/20041/20/2004 12:00:00 AMPPART
The fire sprinkler tamper valves are not supervised by the fire alarm system; when this project is finished the fire alarm control panel will be located outside and will be outside the listing of the panel; submittals are required for the tampers and relocation of the fire alarm panel 1/20/2004 3:13:48 PM