FIR03-00620
| INSP-Final Inspection | 1/16/2004 | 1/20/2004 | 1/20/2004 12:00:00 AM | A | FAIL |
|
|
mark ; Phone #: ###-#### Internet Inspection Request from: Annette Moore smoke detector for FACP located too far down on wall; it will be relocated 1/20/2004 11:37:37 AM
|
FIR03-00070
| INSP-Final Inspection | 1/16/2004 | 1/20/2004 | 1/20/2004 12:00:00 AM | A | PASS |
|
|
###-#### all notification and smoke detectors within this space are on the 2 east panel; the sprinklers are still on the other building zone and plans/installation are in progress 1/20/2004 11:35:34 AM
|
BLD03-02876
| FIRE-Final Inspection | 1/19/2004 | 1/20/2004 | 1/20/2004 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/19/2004 at 10:54:06 AM. Contact: ###-####. not a final inspection but a conference about the alarm system; the alarm system is not required for this occupancy and the system will have to be brought up to current notification/initiation standard or the system removed; submittals are required to do either and to add the new duct detector for the new AHU 1/20/2004 3:25:20 PM
|
BLD03-02848
| FIRE-Final Inspection | 1/19/2004 | 1/20/2004 | 1/20/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/19/2004 at 3:15:33 PM. Contact: ###-####. The fire sprinkler tamper valves are not supervised by the fire alarm panel; the GC will have them added with fire alarm submittals under BLD03-02412 1/20/2004 3:11:22 PM
|
BLD02-02815
| FIRE-Conference | 1/20/2004 | 1/20/2004 | 1/20/2004 12:00:00 AM | A | PART |
|
|
met with Jason and the sprinklers will be on the 2 east sprinkler zone for alarm notification
|
FIR03-00759
| INSP-Final Inspection | 1/20/2004 | 1/20/2004 | 1/20/2004 12:00:00 AM | P | PASS |
|
|
|
BLD03-02412
| FIRE-Conference | 1/20/2004 | 1/20/2004 | 1/20/2004 12:00:00 AM | P | PART |
|
|
The fire sprinkler tamper valves are not supervised by the fire alarm system; when this project is finished the fire alarm control panel will be located outside and will be outside the listing of the panel; submittals are required for the tampers and relocation of the fire alarm panel 1/20/2004 3:13:48 PM
|