Inspections for the day of: Thursday, January 20, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03275 ELE-Aging Inspection1/20/20051/20/20051/20/2005 12:00:00 AM PASS
ELE04-03276 ELE-Aging Inspection1/20/20051/20/20051/20/2005 12:00:00 AM NR
suc 1/21/2005 11:49:32 AM
ELE04-03090 Final1/20/20051/20/20051/20/2005 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jim Williams
fixture in shower shall be listed for wet locations.
bedroom not inspected because the owner said he only changed out the boxes and did no rewire and didnot require a permit. 1/20/2005 9:03:45 AM
ELE04-03663 Final1/20/20051/20/20051/20/2005 12:00:00 AMANR
Scheduled by a contractor via Hello! on 1/20/2005 at 7:26:38 AM. Contact: ###-####.
ELE05-00181 Electrical Rough-In1/19/20051/20/20051/20/2005 12:00:00 AMAPART
Sean; Phone #: ###-#### Internet Inspection Request from: Jan Rice
Walls ok 1/20/2005 10:21:18 AM
ELE05-00185 Electrical Rough-In1/19/20051/20/20051/20/2005 12:00:00 AMAFAIL
Jason-garage only; Phone #: ###-#### Internet Inspection Request from: Jan Rice
raintight connector at service
6 in. free conductor.
outer sheath outside box 1/20/2005 9:26:26 AM
ELE04-03882 Electrical Rough-In1/19/20051/20/20051/20/2005 12:00:00 AMAPART
footing ground, please contact Tom Gilbert. Thank You; Phone #: ###-#### Internet Inspection Request from: Wendy Waters
electrode ok 1/20/2005 10:55:40 AM
ELE04-03949 Temporary Service1/19/20051/20/20051/20/2005 12:00:00 AMAPASS
Justin; Phone #: ###-#### Internet Inspection Request from: Jan Rice
T/S O/H Ok 1/20/2005 10:55:07 AM
ELE04-03319 Final1/20/20051/20/20051/20/2005 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 1/20/2005 at 6:52:19 AM. Contact: ###-####.
had conf 1/20/2005 10:21:42 AM
ELE05-00186 Permanent Service1/19/20051/20/20051/20/2005 12:00:00 AMPPASS
Please call Jon Starke with any questions; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong
P/S O/H R Ok 1/20/2005 2:25:19 PM
ELE05-00192 Temporary Service1/20/20051/20/20051/20/2005 12:00:00 AMPPASS
###-#### michael
T/S U/g Ok 1/20/2005 2:24:57 PM
ELE04-03830 Rough-In Permanent Service1/20/20051/20/20051/20/2005 12:00:00 AMPPART
Jim; Phone #: ###-#### Internet Inspection Request from: Jan Rice
P/S O/H R Ok for power only
line side to disconnect ok
has some grounding to water must redo ground rods.
shall remove hot tub before final
load side not finished. 1/20/2005 3:24:05 PM
ELE04-03663 Final1/20/20051/20/20051/20/2005 12:00:00 AMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Jan Rice