Inspections for the day of: Thursday, January 20, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00593 INSP-Sprinkler Rough-in/Hydro1/19/20051/20/20051/20/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 1/19/2005 at 10:22:06 AM. Contact: ###-####. Air test on preaction failed; air test on dry okay 1/20/2005 9:32:16 AM
FIR04-00575 INSP-Final Inspection1/19/20051/20/20051/20/2005 12:00:00 AMAPASS
Rick, We spoke to the Hoff Building Maintenance man Kevin. He would like to test at 10:00am tomorrow if at all possible. He will notify everyone in the building tonight, so that they may plan ahead. If there is a problem with that time, please let me know as soon as possible, so that we may let the building occupants know when to expect a test. My cell number is ###-#### if you cannot reach me at the office. Thank you for your time. Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
BLD04-01093 FIRE-Final Inspection1/20/20051/20/20051/20/2005 12:00:00 AMAPASS
BLD04-02015 FIRE-Final Inspection1/20/20051/20/20051/20/2005 12:00:00 AMPPASS
Drew; Phone #: ###-#### Internet Inspection Request from: Jan Rice
BLD03-03048 FIRE-Final Inspection1/20/20051/20/20051/20/2005 12:00:00 AMPFAIL
Jim; Phone #: ###-#### Internet Inspection Request from: Jan Rice Extinguishers need annual and at 48 inches; sign above main exit; exit hardware; duct detectors for AHU shutdown 1/20/2005 3:22:58 PM
FIR05-00019 INSP-Final Inspection1/20/20051/20/20051/20/2005 12:00:00 AMPFAIL
Jeff; Phone #: ###-#### Internet Inspection Request from: Jan Rice
FIR04-00727 INSP-Final Inspection1/19/20051/20/20051/20/2005 12:00:00 AMPCANC
bill per rick afer 3:30 ???; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Received call from Pam and this will be rescheduled 1/20/2005 9:46:44 AM
FIR03-00744 INSP-Final Inspection1/18/20051/20/20051/20/2005 12:00:00 AMPCANC
burl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Rescheduled for 1/21 1/20/2005 4:42:46 PM
FIR04-00205 INSP-Sprinkler Rough-in/Hydro1/18/20051/20/20051/20/2005 12:00:00 AMPFAIL
Contact: Jim Danes - Walk Thru Rough-In, Please call to confirm time so Jim can meet you there.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Need head under ductwork in north space; repair flow switch and test monitoring; will need hydro; sign at FDC showing areas sprinklered; sign/door for north aux drain 1/20/2005 4:41:50 PM