Inspections for the day of: Friday, January 20, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04401 Rough-In Permanent Service1/20/20061/20/20061/20/2006 3:50:36 PMPFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cor. fee due posted called more violations created from 1st correction posted, 250.102(C) shall size bond jumper to 250.66, 408.36(F) back fed device clip 120/230 V panel, 300.4 (F) bushings for 4 and larger, 300.10 tighten grd choke fittings, nipples from LBs shall have locknuts both sides of cabinet and be made up tight, everything is loose, 110.12(A) seal all unused KOs
ELE05-03215 Rough-In Permanent Service1/20/20061/20/20061/20/2006 2:43:51 PMPPART
'Cover Inspection' contact Dave at ###-#### if questions .. ; Phone #: ###-#### Internet Inspection Request from: Cathy Felin walls and har ceilings in offices and locker bathrm area, walls in showrm ok
ELE06-00218 Temporary Service1/20/20061/20/20061/20/2006 1:56:57 PMPPASS
Joe-Journeyman; Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s u/g new ok
ELE06-00176 Temporary Service1/20/20061/20/20061/20/2006 1:11:44 PMPPASS
ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford t/s u/g new ok
ELE06-00196 Electrical Rough-In1/20/20061/20/20061/20/2006 10:32:37 AMAPASS
Scheduled by a contractor via Hello! on 1/20/2006 at 7:14:54 AM. Contact: ###-####.walla ceilings ok
ELE06-00118 Electrical Rough-In1/20/20061/20/20061/20/2006 10:31:52 AMAPASS
Scheduled by a contractor via Hello! on 1/20/2006 at 7:13:56 AM. Contact: ###-####. walls ceilings ok
ELE06-00199 Electrical Rough-In1/20/20061/20/20061/20/2006 9:59:49 AMAPART
Phone #: ###-#### Internet Inspection Request from: joe wheeler walls ok
ELE05-04497 Electrical Rough-In1/19/20061/20/20061/20/2006 9:33:35 AMAPASS
Donna -- ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth ok
ELE05-04047 Final1/19/20061/20/20061/20/2006 9:05:38 AMAFAIL
Scheduled by a contractor via Hello! on 1/19/2006 at 3:36:56 PM. Contact: ###-####. cor. fee due posted called 314.17 needs connectors at bell boxes for cables, 225.30 detached garage shall have only one branch circuit or feeder, 225.31,32 provide disconnect at required location
ELE06-00218 Temporary Service1/19/20061/20/20061/20/2006 8:29:39 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: William Zerfas cor. called 312.5 conn for GEC, 250.24 terminate GEC at neutral
ELE05-03136 Final1/19/20061/20/20061/20/2006 8:10:13 AMAFAIL
garage code is 1234 Internet Inspection Request from: Cevyn Recla correction not made still needs clearence, or remove wiring coat closet under stairs called
ELE05-04541 Conference1/20/20061/20/20061/20/2006 12:00:00 AMPDONE
ok
ELE06-00223 Rough-In Permanent Service1/19/20061/20/20061/19/2006 2:26:47 PMAPASS
darrell ###-#### r/i ok p/s u/g new ok