Inspections for the day of: Tuesday, January 20, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy James
TitleMEC-COM/RES INSPECTOR
Phone #794-9461
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC09-00105 Rough-in1/20/20091/20/20091/20/2009 12:58:35 PMPFAIL
air care Phone #: ###-####
bath fan needs to ducted, may need smoke detector added if one is not there, need to verify
MEC08-03646 Final1/20/20091/20/20091/20/2009 11:11:23 AMPPASS
Phone #: ###-#### Internet Inspection Request from: GREG ANDERSEN
MEC08-03587 Final1/20/20091/20/20091/20/2009 11:11:12 AMAFAIL
need sediment trap before gas regulator and turn regulator upright with maxitrol vent cap
MEC08-03178 Final1/19/20091/20/20091/20/2009 10:50:55 AMAFAIL
INSTALLATION INSTRUCTIONS ON SITE POTS IN Phone #: ###-#### Internet Inspection Request from: Denton Fuehrer
cabinets not installed per manufacturer of range and mantel is non-compliant at fireplace
MEC09-00102 Rough-in1/19/20091/20/20091/20/2009 10:27:11 AMAPASS
If the house is locked up, the lock box code is 782. Please call me with any questions. Thank you Phone #: ###-#### Internet Inspection Request from: 4 Seasons
ok to cover ducts only, no gas piping
MEC04-02614 DOC - Permit Expired1/20/20091/20/20091/20/2009 9:53:00 AMPPASS
MEC04-02614 Pressure Test1/20/20091/20/20091/20/2009 9:52:14 AMACANC
We are hanging the hood today also but we need the pressure test so we can fire the range. Phone #: ###-#### Internet Inspection Request from: Veronica Shipley
scheduled in error
MEC08-03633 Final1/16/20091/20/20091/20/2009 9:37:52 AMAPASS
Brandon Phone #: ###-####
MEC09-00094 Final1/16/20091/20/20091/20/2009 9:09:22 AMAPASS
meet bill at 8:30am