FIR09-00567
| FIR-Aging Inspection | 1/20/2010 | 1/20/2010 | 1/22/2010 10:45:07 AM | | NR |
|
|
Per mike with Allied this permit will be called in for inspection within the next two weeks.
|
FIR10-00021
| INSP-Final Inspection | 1/20/2010 | 1/20/2010 | 1/20/2010 4:01:48 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00744
| INSP-Final Inspection | 1/20/2010 | 1/20/2010 | 1/20/2010 3:40:55 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00021
| INSP-Alarm Testing | 1/20/2010 | 1/20/2010 | 1/20/2010 3:02:00 PM | P | PASS |
|
|
Permit finaled.
|
BLD09-00557
| FIRE-Conference | 1/20/2010 | 1/20/2010 | 1/20/2010 1:56:08 PM | P | DONE |
|
|
The stop work order that had been previously posted for the fire alarm installation is being lifted due to the fire alarm plans being issued.
|
FIR09-00711
| INSP-Conference | 1/19/2010 | 1/20/2010 | 1/20/2010 1:55:41 PM | A | DONE |
|
|
The stop work order that had been previously posted for the fire alarm installation is being lifted due to the fire alarm plans being issued.
|
FIR09-00744
| INSP-Final Inspection | 1/20/2010 | 1/20/2010 | 1/20/2010 1:53:15 PM | P | FAIL |
|
|
Did not perform inspection due to the manual actuation device not meeting IFC 904.11.1. To be rescheduled. No testing was performed.
|
BLD09-01035
| FIRE-Final Inspection | 1/20/2010 | 1/20/2010 | 1/20/2010 1:34:01 PM | P | PASS |
|
|
Life safety passed.
|
BLD09-01035
| FIRE-Final Inspection | 1/19/2010 | 1/20/2010 | 1/20/2010 11:51:15 AM | A | FAIL |
|
|
The duct smoke detector has been oriented incorrectly, has the wrong length of sample tube and does not shut down the hvac system when tested in heat mode.
|
FIR10-00020
| INSP-Final Inspection | 1/19/2010 | 1/20/2010 | 1/20/2010 11:48:37 AM | A | PASS |
|
|
The hood suppression system functioned correctly. Two sink were relocated so that the refrigerator could be relocated from under the hood.
|
BLD09-01808
| FIRE-Final Inspection | 1/19/2010 | 1/20/2010 | 1/20/2010 11:46:57 AM | A | FAIL |
|
|
This project is not ready for inspection. Will be rescheduled for monday.
|
BLD09-02162
| FIRE-Final Inspection | 1/19/2010 | 1/20/2010 | 1/20/2010 10:18:44 AM | A | PASS |
|
|
Life safety passed. The remaining emergency lights have been repaired.
|