Inspections for the day of: Friday, January 20, 2012.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00521 FIR-Aging Inspection1/20/20121/20/20121/23/2012 2:56:04 PM NR
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
FIR10-00033 FIR-Aging Inspection1/20/20121/20/20121/23/2012 2:55:51 PM NR
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
FIR10-00429 FIR-Aging Inspection1/20/20121/20/20121/23/2012 2:55:31 PM NR
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
FIR11-00671 INSP-Sprinkler Rough-in1/19/20121/20/20121/20/2012 3:55:52 PMPCANC
As late in the day as possible. Nate is the contact. Thanks Phone #: ###-#### Overbooked due to other inspections and Micron facilities plan review.
FIR11-00371 INSP-Sprinkler Rough-in1/20/20121/20/20121/20/2012 3:54:28 PMPCANC
kevin Phone #: ###-#### Overbooked due to other inspections and Micron facilities plan review.
BLD11-02585 FIRE-Conference1/20/20121/20/20121/20/2012 3:47:24 PMPDONE
Jr and I went over life safety requirements which include the possible demolishion of an existing fire alarm system or making sure it is functional. Door hardware needs to be compliant as well as repairing/adding exit signs and emergency lights and fire extinguishers.
FIR11-00479 INSP-Conference1/19/20121/20/20121/20/2012 3:30:24 PMPDONE
Mike and I discussed not installing the two pendant heads in the soffit surrounding the sky light in the main entry/lobby. It is less than 4' at all points and typically only 18" wide. The sky light is covered by a sidewall sprinkler head. I'm ok with deleting the two soffit pendants. We also discussed scheduling cover inspections for the remaining areas
FIR12-00013 INSP-Supply line flush1/19/20121/20/20121/20/2012 12:39:08 PMPFAIL
The underground supply line is not buried deep enough, has been installed as 1 1/2" without the 2" starter and is not a continous run to the riser as shown on the plans.
FIR11-00641 INSP-Sprinkler Rough-in1/19/20121/20/20121/20/2012 12:23:30 PMAPASS
Sprinkler piping is ok to cover.
FIR12-00005 INSP-Final Inspection1/19/20121/20/20121/20/2012 12:22:56 PMAFAIL
Provide earthquake bracing as discussed and branchline restraints.
BLD11-02973 FIRE-Alarm Testing1/19/20121/20/20121/20/2012 10:52:14 AMADONE
This was a pre-inspection for the fire alarm scope of work. It appears the device spacing is adequate. I discussed the need for EOL voltage verification.
FIR11-00688 INSP-Sprinkler Rough-in/Hydro1/19/20121/20/20121/20/2012 10:49:55 AMADONE
This was a pre-inspection. I found strobe coverage overspaced off of the breakroom wall. I discussed the need for EOL voltage verification.
BLD11-03014 FIRE-Final Inspection1/19/20121/20/20121/20/2012 10:25:35 AMAPASS
life safety passed
BLD11-03013 FIRE-Final Inspection1/19/20121/20/20121/20/2012 10:24:56 AMAPASS
life safety passed