Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00542 ELE-Aging Inspection1/20/20151/20/20151/27/2015 11:22:53 AM DONE
Drove by for sale sign posted. Will check to see if open permit is issue with sale.
ELE15-00096 Final1/16/20151/20/20151/20/2015 2:21:26 PMPPASS
Diana Phone #: ###-#### Final ok
ELE14-02675 Permanent Service1/20/20151/20/20151/20/2015 1:44:08 PMPPASS
Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Metal water pipe bond to be done when pipe present. p/s u/g n ok
ELE14-03399 Electrical Rough-In1/19/20151/20/20151/20/2015 1:11:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Jay Symonds Garage rough in ok cover
ELE14-03238 Rough-In Permanent Service1/20/20151/20/20151/20/2015 12:49:54 PMPPASS
Radiant floor heat in bathroom only.

Thank you, Phone #: ###-#### Inspection requested via web by Rhonda Zamagni Floor heat rough in ok cover
ELE14-02943 Final1/20/20151/20/20151/20/2015 12:18:53 PMAPASS
Josh is contact thank you Phone #: ###-#### Inspection requested via web by Chris Chesnut No record of floor heat rough in, listing confirmed. At time of final lights in master closet and light over bath tub ok. Final ok
ELE15-00113 Electrical Rough-In1/16/20151/20/20151/20/2015 11:40:09 AMAPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Entrance on back south east corner. Reception and break room wall rough in ok cover
ELE14-02675 Permanent Service1/19/20151/20/20151/20/2015 11:22:54 AMAFAIL
Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 250.24(A)(1)- The grounding electrode conductor connection shall be made at the same terminal or bus to which the grounded conductor is connected.
250.50- All available grounding electrodes shal be used to form grounding electrode system.
ELE15-00125 Electrical Rough-In1/19/20151/20/20151/20/2015 9:56:40 AMAPASS
Wall cover in floral area. Dan Lowry is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen 3, 1/2 walls to south of old location rough in ok cover
ELE14-03277 Rough-In Permanent Service1/19/20151/20/20151/20/2015 9:33:37 AMACANC
Phone #: ###-#### Inspection requested via web by ron spen cer Wrong permit for request, refer to ele15-00126
ELE15-00126 Permanent Service1/20/20151/20/20151/20/2015 9:33:20 AMPFAIL
310.15(B)(7)- In no case shall the service entrance conductors be sized less than 83% of the service rating. 125 amp x 83%= 103.75 amps. Table 310.15(B)(16)- 75* #2 minimum size required.
ELE15-00126 Electrical Rough-In1/20/20151/20/20151/20/2015 9:25:32 AMPPASS
Rough in ok cover
ELE15-00126 Rough-In Permanent Service1/20/20151/20/20151/20/2015 9:24:49 AMPCANC
See rough in
ELE15-00046 Rough-In Permanent Service1/16/20151/20/20151/20/2015 8:41:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Dan Rohl Rough in ok cover p/s u/g n ok