Inspections for the day of: Wednesday, January 20, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01940 ELE-Aging Inspection1/20/20161/20/20161/22/2016 11:25:34 AM PASS
Drove by and inspected
ELE13-00804 ELE-Aging Inspection1/20/20161/20/20161/20/2016 2:46:38 PM DONE
Still under construction
ELE13-01944 ELE-Aging Inspection1/20/20161/20/20161/20/2016 2:45:59 PM DONE
Drove by and inspected
ELE13-01944 Final1/20/20161/20/20161/20/2016 2:33:51 PMPPASS
UL listing confirmed. Final ok
MIS16-00015 ELE-Conference1/20/20161/20/20161/20/2016 2:31:11 PMPDONE
4-05-32- Code violations not to be retained.
While on site for service change inspection under permit ELE16-00171 noticed hot tub branch circuit to back of garage wrapped around truss for support. Checked rest of installation found following.
4-05-18- Permit required for installation of hot tub.
334.12(B)(4)- NM cable shall not be installed in a wet location. Exposed out doors and underground.
334.15(B)-NM cable shall not installed where subject to physical damage. Exposed on exterior of house below disconnect and emerges from underground and enters tub with out protection.
300.4(B)(1)- Where NM cable passes through either factory or field punched, cut, or drilled holes in metal members the cable shall be protected by listed bushing or grommets covering all metal edges. At disconnect need to check tub.
680.26(B)(7)- Fixed metal parts including awnings shall be bonded
ELE16-00171 Rough-In Permanent Service1/19/20161/20/20161/20/2016 1:54:10 PMPPASS
Please call Matt ###-#### to make sure they are ready for you. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
Service change p/s u/g rec ok
ELE15-01099 Electrical Rough-In1/20/20161/20/20161/20/2016 1:45:47 PMPPASS
Randall Phone #: ###-####
Owner ran low voltage wire to same box as line voltage, he will pick up divider for 3 gang box on TV wall. Master bath upstairs rough in ok cover
ELE16-00182 Electrical Rough-In1/19/20161/20/20161/20/2016 12:41:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Cyndi Dale
North end of building. Demising wall rough in ok cover
ELE16-00112 Permanent Service1/19/20161/20/20161/20/2016 11:17:03 AMAPASS
Nick Phone #: ###-####
250.58 Common Grounding Electrode. Where an ac system is connected to a grounding electrode in or at a building or structure, the same electrode shall be used to ground conductor enclosures and equipment in or on that building or structure. Where separate services, feeders, or branch circuits supply a building and are required to be connected to a grounding electrode(s), the same grounding electrode(s) shall be used. Will check next trip.
110.24- Available fault current shall be posted with date calculated. 200k rated fuses installed.
p/s u/g n ok
ELE16-00183 Electrical Rough-In1/19/20161/20/20161/20/2016 10:22:45 AMAPASS
Mike Phone #: ###-####
Conference room under slab to floor box rough in ok cover
ELE16-00188 Permanent Service1/20/20161/20/20161/20/2016 9:45:29 AMAFAIL
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering.
THERE IS MOLD IN THIS HOME, WEAR A MASK
ACCESS CODE IS 2230, Thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren
110.12(A)- Unused openings shall be closed. Breaker
110.12(B)-Hot tub circuit shall be totally removed. Wire damage due to undersized for load served.
No access due to black mold and I did not have a mask to verify plumbing bond.
ELE15-04109 Permanent Service1/20/20161/20/20161/20/2016 9:00:54 AMAPASS
Service Inspection. Contact Travis Hust Phone #: ###-#### Inspection requested via web by Cathy Duchek p/s o/h n ok