ELE03-03316
| ELE-Aging Inspection | 1/21/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | | NR |
|
|
stopped at job site sign not wired and no permit yet for a contractor 1/21/2004 4:16:43 PM
|
ELE03-03562
| ELE-Aging Inspection | 1/21/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | | PASS |
|
|
disconnect installed 1/21/2004 12:45:03 PM
|
ELE03-04069
| Final | 1/20/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/20/2004 at 11:12:38 AM. Contact: ###-####. ok 1/21/2004 8:40:12 AM
|
ELE03-03702
| Final | 1/20/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | A | FAIL |
|
|
Michael; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes cor. posted met owner needs gfci for garage recepts 1/21/2004 10:45:48 AM
|
ELE04-00140
| Electrical Rough-In | 1/20/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | A | PART |
|
|
###-#### JIM walls ok 1/21/2004 10:46:01 AM
|
ELE04-00130
| Electrical Rough-In | 1/20/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 1/20/2004 at 3:01:05 PM. Contact: ###-####. walls ok 1/21/2004 9:38:42 AM
|
ELE04-00092
| Electrical Rough-In | 1/20/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | P | FAIL |
|
|
call 1st before insp jim- ###-#### cor. posted met owner 300.4, 210.52(A) , 250 148, 334.30&314.17(A), 300.14, 110.12(A), 314.17, replace 2&3 gang boxes with broken clamps, 352.30 (A), 310.15(B) derate for over 10 wires in conduit, 250.22(B) proper size equip grd for deration, 110.3(B)& BCC no violations retained for breakers non GE and owner work done without permit 3 years ago in old part of house "COW" do not cover posted 1/21/2004 2:23:34 PM
|
ELE03-03532
| Final | 1/20/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 1/20/2004 at 8:27:47 PM. Contact: ###-####. ok 1/21/2004 12:06:24 PM
|
ELE04-00147
| Permanent Service | 1/21/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | P | CANC |
|
|
meter panel outside- thomas- ###-####-- call 1st before insp for access called owner not available today he will have contractor reschedule 1/21/2004 3:33:23 PM
|
ELE03-02472
| Final | 1/21/2004 | 1/21/2004 | 1/21/2004 12:00:00 AM | P | PART |
|
|
WITH ANY QUESTIONS PLEASE CALL LUKE BUSACK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford temp occupancy for area north of corridor, brain scan 1/21/2004 3:25:15 PM
|